Honeywell NX4S1 Installation Guide - Page 59

Technical Support

Page 59 highlights

NetAXS™ NX4S1 Installation Technical Support Table 8 Troubleshooting Problems and Solutions Problem Solution A dropline panel in standalone mode using RS-232 may unexpectedly fill its buffer. The preferred solution is to configure the standalone panel through the Web server as a Gateway and use the board PCI and AckNak communications. This also gives the user a more secure and reliable communications line. Another solution is to execute a new command that will allow the user to turn the Tesla flow control off : _U=_D (disable flow control) This prevents the panels from inadvertently filling their buffers. To turn the Tesla flow control back on: _U=_E (enable flow control) Note: The NetAXS™ EOL network is AC-coupled. There is no resistance difference between the RS-485 positive and negative terminals if the EOL network is on or off (J36 and J37). 10.0 Technical Support 10.1 Normal Support Hours Monday through Friday, 7:00 a.m. to 7:00 p.m. Central Standard Time (CST), except company holidays: (800) 323-4576. 10.2 Web For technical assistance please visit http://www.honeywellaccess.com NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008, Revision A 49

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73

NetAXS™ NX4S1 Installation
Technical Support
NetAXS Access Control Unit NX4S1 Installation Guide
,
Document 800-00008, Revision A
49
Note:
The NetAXS™ EOL network is AC-coupled. There is no resistance difference
between the RS-485 positive and negative terminals if the EOL network is on or off
(J36 and J37).
10.0
Technical Support
10.1
Normal Support Hours
Monday through Friday, 7:00 a.m. to 7:00 p.m. Central Standard Time (CST), except
company holidays: (800) 323-4576.
10.2
Web
For technical assistance please visit http://www.honeywellaccess.com
A dropline panel
in standalone
mode using
RS-232 may
unexpectedly fill
its buffer.
The preferred solution is to configure the standalone panel through the
Web server as a Gateway and use the board PCI and AckNak communi-
cations.
This also gives the user a more secure and reliable communi-
cations line.
Another solution is to execute a new command that will allow the user
to turn the Tesla flow control off :
_U=<pn>_D
(disable flow control)
This prevents the panels from inadvertently filling their buffers.
To turn the Tesla flow control back on:
_U=<pn>_E
(enable flow control)
Table 8