Honeywell NX4S1 Installation Guide - Page 59
Technical Support
View all Honeywell NX4S1 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 59 highlights
NetAXS™ NX4S1 Installation Technical Support Table 8 Troubleshooting Problems and Solutions Problem Solution A dropline panel in standalone mode using RS-232 may unexpectedly fill its buffer. The preferred solution is to configure the standalone panel through the Web server as a Gateway and use the board PCI and AckNak communications. This also gives the user a more secure and reliable communications line. Another solution is to execute a new command that will allow the user to turn the Tesla flow control off : _U=_D (disable flow control) This prevents the panels from inadvertently filling their buffers. To turn the Tesla flow control back on: _U=_E (enable flow control) Note: The NetAXS™ EOL network is AC-coupled. There is no resistance difference between the RS-485 positive and negative terminals if the EOL network is on or off (J36 and J37). 10.0 Technical Support 10.1 Normal Support Hours Monday through Friday, 7:00 a.m. to 7:00 p.m. Central Standard Time (CST), except company holidays: (800) 323-4576. 10.2 Web For technical assistance please visit http://www.honeywellaccess.com NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008, Revision A 49