Honeywell NX4S1 Installation Guide - Page 67
A.3.6, W Input Command, A.3.7, P Interlock Command
View all Honeywell NX4S1 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 67 highlights
NetAXS™ Standalone Operation Standalone Commands A.3.6 W (Input) Command _W=pn_input_{SO|SC|NO|NC} Variables: SO: Supervised normally open SC: Supervised normally closed NO: Non-supervised normally open NC: Non-supervised normally closed (default) Example: _W=1_9_SO Input 9 has been programmed as supervised, normally open on panel 1. A.3.7 P (Interlock) Command _P=pn_I/O_[number]_I/O[number]_{D|E|F|N|P}_ {D|E|F|N|P} Parameters: number: for an input number, the range is 1-96; for output, 0-78 D: De-energize E: Energize F: Follow N: No action P: Pulse Example: _P=1_I_5_O_3_E_D When Input 5 is triggered, Output 3 energizes. When Input 5 returns to its normal state, Output 3 de-energizes. NetAXS Access Control Unit NX4L1 Installation Guide, 7-901099, Revision A 57