Honeywell NX4S1 Installation Guide - Page 49

Fiber Converter to RS-485 Connection via NetAXS™

Page 49 highlights

NetAXS™ NX4S1 Installation System Configuration 5.13 Fiber Converter to RS-485 Connection via NetAXS™ This connection supports thirty-one NetAXS™ Access Controller panels for each drop line. It has not been reviewed by UL. Figure 29: Fiber Converter to RS-485 Connection via NetAXS™ COM Port RS-232 (50 Ft. Max.) RS-485 (4000 Ft. Max.) Terminal FC485 EG RS-485 Fiber Converter RXD PWR TXD RS-485 Comm. RS-485 Positive (+) RS-485 Negative (-) Fiber RXD Fiber TXD EG DIP Switch Settings S1-S5 Panel Address S6: OFF J36: CLOSED J37: CLOSED ) h ground FC485 RS-485 Fiber Converter RXD PWR TXD RS-485 Comm. RS-485 Positive (+) RS-485 Negative (-) Fiber RXD Fiber TXD FC485 RS-485 Fiber Converter RXD PWR TXD RS-485 Comm. RS-485 Positive (+) RS-485 Negative (-) Fiber RXD Fiber TXD EG It is recommended to Earth Ground (EG) each NetAXS enclosure Individually NetAXS Panel EG EG EG DIP Switch Settings S1-S5 Panel Address S6: OFF J36: OPEN J37: OPEN FC485 RS-485 Fiber Converter RXD PWR TXD RS-485 Comm. RS-485 Positive (+) RS-485 Negative (-) Fiber RXD Fiber TXD RS-485 Cable NetAXS Panels TB7-1 (RS485+) TB7-2 (RS485-) TB7-3 (RS485 COM) 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN) NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008, Revision A 39

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73

NetAXS™ NX4S1 Installation
System Configuration
NetAXS Access Control Unit NX4S1 Installation Guide
,
Document 800-00008, Revision A
39
5.13
Fiber Converter to RS-485 Connection via NetAXS™
This connection supports thirty-one NetAXS™ Access Controller panels for each drop line. It has not
been reviewed by UL.
Figure 29:
Fiber Converter to RS-485 Connection via NetAXS™
COM Port
RS-485
(4000 Ft. Max.)
RS-232 (50 Ft. Max.)
FC485
RS-485 Fiber Converter
FC485
RS-485 Fiber Converter
RXD
PWR
TXD
RXD
PWR
TXD
RS-485 Comm.
RS-485 Positive (+)
RS-485 Negative (-)
RS-485 Comm.
RS-485 Positive (+)
RS-485 Negative (-)
Fiber RXD
Fiber TXD
Fiber RXD
Fiber TXD
)
h ground
NetAXS
Panel
RXD
PWR
TXD
RS-485 Comm.
RS-485 Positive (+)
RS-485 Negative (-)
Fiber RXD
Fiber TXD
RXD
PWR
TXD
RS-485 Comm.
RS-485 Positive (+)
RS-485 Negative (-)
Fiber RXD
Fiber TXD
EG
EG
EG
EG
EG
EG
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: OPEN
J37: OPEN
It is recommended to
Earth Ground (EG)
each NetAXS enclosure
Individually
FC485
RS-485 Fiber Converter
FC485
RS-485 Fiber Converter
RS-485 Cable
NetAXS Panels
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
Terminal