Honeywell NX4S1 Installation Guide - Page 63
Standalone Commands
View all Honeywell NX4S1 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 63 highlights
NetAXS™ Standalone Operation Standalone Commands A.3 Standalone Commands Use the following commands, in the order they are listed, to configure the NetAXS™ panel. 1. T command: Sets the panel's Time 2. D command: Sets the panel's Date 3. L command: Creates Time zones for use by the cards 4. C command: Adds or Deletes cards from the panel 5. W command: Program each input for either NO/NC and Supervised or NON Supervised operation 6. P command: Sets interlocks between input points and/or output points Note: In all examples, the underbar "_" indicates a "space" character and indicates a carriage return. A.3.1 T (Time) Command _T=pn_hh:mm Variables: pn = panel number (1-31) hh = hours (0-23) (Military time) mm = minutes (00-59) Example #1: _T=1_08:30 This command would set panel 1 to a time of 8:30 AM. Example #2 _T=6_18:15 This command would set panel 6 to a time of 6:15 PM. NetAXS Access Control Unit NX4L1 Installation Guide, 7-901099, Revision A 53