Honeywell NX4S1 Installation Guide - Page 51
NetAXS™/NetAXS™ Access Controller Panel Connection Detail
View all Honeywell NX4S1 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 51 highlights
NetAXS™ NX4S1 Installation System Configuration 5.15 NetAXS™/NetAXS™ Access Controller Panel Connection Detail Figure 31: NetAXS™/NetAXS™ Access Controller Panel Connection Detail Ground Shield X DO NOT CONNECT or GROUND SHIELD To Serial Connection NetAXS TB7 1 2 3 NetAXS TB7 1 2 3 DIP Switch Settings S1-S5:Panel Address S6: ON J36: CLOSED J37: CLOSED DIP Switch Settings S1-S5:Panel Address S6: OFF J36: CLOSED J37: CLOSED DIP Switch Settings S1-S5:Panel Address S6: OFF J36: OPEN J37: OPEN NetAXS Panel 3 1 2 DO NOT CONNECT SHIELD X 485 Common Shield 485 + 485 - NetAXS TB7 Ground only one side of cable shield 4,000 ft.(1,200 m) max,24 AWG,2 twisted pairs with shield,120 ohm,23 pf (NCI part no.NCP2441-TN) NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008, Revision A 41