Honeywell NX4S1 Installation Guide - Page 71
A.4.5, Door Status Inputs, A.4.6, ACFAIL and Panel Tamper Inputs
View all Honeywell NX4S1 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 71 highlights
NetAXS™ Standalone Operation NetAXS™ Panel Defaults A.4.5 Door Status Inputs The panel has a Door Status input for each door. The default condition is a two-state input configured as a Normally Closed contact. The following are the default door status input associations: Door Status input Panel input 1 SP2 1 SP4 1 SP6 1 SP8 Reports as... Input 2 Input 4 Input 6 Input 8 A.4.6 ACFAIL and Panel Tamper Inputs The panel has the following two additional generic inputs that can be used as generic inputs or as either External Power Fail or Enclosure Tamper inputs. The default condition is a two-state input configured as Normally Closed. Input 14 is a special case, since it reports in as two inputs (inputs 14 and 20). Input 14 can be used as a generic input, but input 20 is used for the Enclosure Tamper alarm. An active External Power Fail input indicates that the system is operating from the battery current, not from the primary input power. An inactive External Power Fail input indicates that the system is operating from the primary input power. Generic input Generic/External Power Fail Generic/Enclosure Tamper Panel input SP9 SP10 Reports as... Input 13 Inputs 14 and 20 NetAXS Access Control Unit NX4L1 Installation Guide, 7-901099, Revision A 61