GE 60-806-95R-16Z Installation Instructions - Page 17

Connecting Sirens - concord express alarm

Page 17 highlights

+12V 4 2k Ohm EOL Resistor (49-454) Locate at Last Device O U T2/ ZO N E OC 1 8 9 ZC O M 1 0 Panel Terminal 8 (OUT2/OC) Must be Set to Configuration Number 01500 for Connected Smoke Detectors to Reset After Canceling a Fire Alarm CC OONN +. +. .- .- M. M. O. O. Model 449AT CC OONN +. +. .- .- M. M. O. O. 2k Ohm EOL Resistor (49-454) Locate at Last Device Model 449AT Note Install all sirens/speakers indoors, in a concealed location. Note If the backup battery is not connected, or if the configuration of panel terminal 7 is programmed to anything other than the default (00410), then the combined currents of terminal 7 (OUT 1/+12) and terminal 4 (+12V) must not exceed 750 mA. Figure 11. Connecting 4-Wire Smoke Detectors Connecting Sirens Two onboard programmable outputs allow for siren connections when using the default setting of each output. For more information on output configuration numbers, see the section "Programming the Panel" and the tables in Appendix A. The following describes siren connections using the default settings of each onboard output. 15-Watt, Dual Tone Siren (13-469) Panel terminal 7 (OUT1/+12V) is a +12V programmable output. At the default configuration setting (00410), this output can provide up to 1.25 A during an alarm (650 mA for UL Listed systems) if the backup battery is connected. The default configuration setting (00410) activates the output during any audible alarm, allowing for a siren connection without changing the output configuration number. Note For UL Listed systems, Siren Verify must be on. Black (Common) Yellow (Steady) GND Concord Express Panel Terminals 3 O U T1/ +12V 7 Red (Not Used) 60806G 100D D S F Figure 12. Connecting 15-Watt, Dual-Tone Siren 13-469 Installing the System 12

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76

Installing the System
12
Figure 11.
Connecting 4-Wire Smoke Detectors
Connecting Sirens
Note
Install all sirens/speakers
indoors, in a concealed loca-
tion.
Two onboard programmable outputs allow for siren connections when using the default setting
of each output. For more information on output configuration numbers, see the section “Pro-
gramming the Panel” and the tables in Appendix A.
The following describes siren connections using the default settings of each onboard output.
Note
If the backup battery is not
connected, or if the configu-
ration of panel terminal 7 is
programmed to anything
other than the default
(00410), then the combined
currents of terminal 7 (OUT
1/+12) and terminal 4 (+12V)
must not exceed 750 mA.
15-Watt, Dual Tone Siren (13-469)
Panel terminal 7 (OUT1/+12V) is a +12V programmable output. At the default configuration
setting (00410), this output can provide up to 1.25 A during an alarm (650 mA for UL Listed
systems) if the backup battery is connected.
The default configuration setting (00410) activates the output during any audible alarm, allow-
ing for a siren connection without changing the output configuration number.
Note
For UL Listed systems,
Siren Verify must be on.
Figure 12.
Connecting 15-Watt, Dual-Tone Siren 13-469
9
10
ZO
N
E
1
ZC
O
M
8
O
U
T2/
O
C
+
C
O
M
. . . . . . . .
+
-
-
C
O
M
N
O
N
O
+
C
O
M
. . . . . . . .
+
-
-
C
O
M
N
O
N
O
4
+12V
Panel Terminal 8 (OUT2/OC)
Must be Set to Configuration
Number 01500 for Connected
Smoke Detectors to Reset
After Canceling a Fire Alarm
2k Ohm
EOL Resistor
(49-454)
Locate at
Last Device
Model
449AT
Model
449AT
2k Ohm
EOL Resistor
(49-454)
Locate at
Last Device
60806G
100D
D
S
F
3
G
N
D
7
O
U
T1/
+12V
Black (Common)
Yellow (Steady)
Red
(Not Used)
Concord
Express
Panel
Terminals