GE 60-806-95R-16Z Installation Instructions - Page 43

Sensors Menu, Disable Trouble Beeps 0601, UL 98 Options 0602, Siren Verify 0610

Page 43 highlights

Disable Trouble Beeps (0601) Siren Options-Global (Default=off) This setting determines whether or not the panel activates trouble beeps when a wireless device supervisory condition is detected. Note For UL Listed systems, this feature must be off. ¾ To turn Disable Trouble Beeps off or on: 1. With the display showing DISABLE TR BEEPS OFF/ON (current setting), press 1 (off) or 2 (on). The display flashes the entered setting. 2. Press ƒ and the display shows the new setting. UL 98 Options (0602) Siren Options-Global (Default=off) This setting determines whether or not the panel complies with UL 98 require- ¾ To turn UL 98 Options off or on: ments (4-hour trouble beep restart, 4-hour backup battery test, 2-hour supervi- 1. With the display showing UL 98 OPTIONS sory time period for sensor group 26-Fire). OFF/ON (current setting), press 1 (off) or 2 Note (on). The display flashes the entered setting. For UL Listed systems, this feature must be on. 2. Press ƒ and the display shows the new set- ting. The following describes how to program the settings that appear under SIREN OPTIONS- PARTITION 1. Siren Verify (0610) Siren Options-Partition 1 (Default=off) This setting determines whether or not the panel monitors sirens connected to panel terminal 7 (OUT1/+12V). When this feature is on, sirens connected to panel terminals 3 (GND) and 7 (OUT1/+12V) require a 2k end-of-line resistor. Refer to "Installing the System-Connecting Sirens" for complete details. Note For UL Listed systems, this feature must be on. ¾ To turn Siren Verify off or on: 1. With the display showing SIREN VERIFY OFF/ON (current setting), press 1 (off) or 2 (on). The display flashes the entered setting. 2. Press ƒ and the display shows the new setting. Note If 2-wire smoke detectors are connected to hardwire zone input 6, the Two-wire Smoke setting must be turned on before entering the LEARN SENSORS menu. See ONBOARD OPTIONS- INPUTS. Sensors Menu The SENSORS menu gives you access to the following: • LEARN SENSORS-lets you learn hardwire zones and wireless sensors into panel memory and assign zones/sensors to specific partitions. • SENSOR TEXT-lets you program sensor text for zone/sensor identification. • DELETE SENSORS-lets you delete zones/sensors from panel memory. • EDIT SENSORS-lets you view and/or change sensor/zone group assignment, view sensor number and text assignments of learned sensors/zones, identify whether zone is wireless or hardwire, and indicates sensor/zone/touchpad input N/C or N/O configuration. The following describes how to program the sensor settings that appear under LEARN SENSORS. Programming the Panel 38

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76

Programming the Panel
38
The following describes how to program the settings that appear under
SIREN OPTIONS—
PARTITION 1
.
Sensors Menu
Note
If 2-wire smoke detectors
are connected to hardwire
zone input 6, the Two-wire
Smoke setting must be
turned on
before
entering
the
LEARN SENSORS
menu.
See
ONBOARD OPTIONS—
INPUTS
.
The
SENSORS
menu gives you access to the following:
LEARN SENSORS
—lets you learn hardwire zones and wireless sensors into panel memory and
assign zones/sensors to specific partitions.
SENSOR TEXT
—lets you program sensor text for zone/sensor identification.
DELETE SENSORS
—lets you delete zones/sensors from panel memory.
EDIT SENSORS
—lets you view and/or change sensor/zone group assignment, view sensor
number and text assignments of learned sensors/zones, identify whether zone is wireless or
hardwire, and indicates sensor/zone/touchpad input N/C or N/O configuration.
The following describes how to program the sensor settings that appear under
LEARN SENSORS
.
Disable Trouble Beeps (0601)
Siren Options-Global (Default=off)
This setting determines whether or not the panel activates trouble beeps when
a wireless device supervisory condition is detected.
Note
For UL Listed systems, this feature must be off.
¾
To turn Disable Trouble Beeps off or on:
1.
With the display showing
DISABLE TR BEEPS
OFF/ON
(current setting)
, press
1
(off) or
2
(on). The display flashes the entered setting.
2.
Press
ƒ
and the display shows the new set-
ting.
UL 98 Options (0602)
Siren Options-Global (Default=off)
This setting determines whether or not the panel complies with UL 98 require-
ments (4-hour trouble beep restart, 4-hour backup battery test, 2-hour supervi-
sory time period for sensor group 26—Fire).
Note
For UL Listed systems, this feature must be on.
¾
To turn UL 98 Options off or on:
1.
With the display showing
UL 98 OPTIONS
OFF/ON
(current setting)
, press
1
(off) or
2
(on). The display flashes the entered setting.
2.
Press
ƒ
and the display shows the new set-
ting.
Siren Verify (0610)
Siren Options-Partition 1 (Default=off)
This setting determines whether or not the panel monitors sirens connected to
panel terminal 7 (OUT1/+12V).
When this feature is on, sirens connected to panel terminals 3 (GND) and 7
(OUT1/+12V) require a 2k end-of-line resistor. Refer to “Installing the Sys-
tem—Connecting Sirens” for complete details.
Note
For UL Listed systems, this feature must be on.
¾
To turn Siren Verify off or on:
1.
With the display showing
SIREN VERIFY
OFF/ON
(current setting)
, press
1
(off) or
2
(on). The display flashes the entered
setting.
2.
Press
ƒ
and the display shows the new
setting.