Panasonic CS-E18SD3UAW service manual - Page 57

Cooling Overload Control, Dew Prevention Control 1, Freeze Prevention Control

Page 57 highlights

13.2.2 Cooling Overload Control i. Pipe temperature limitation/restriction  Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation frequency)  The compressor stop if outdoor pipe temperature exceeds 145.4°F.  If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95: outdoor high pressure rise protection) 13.2.3 Dew Prevention Control 1 1 To prevent dew formation at indoor unit discharge area. 2 This control activated if: o Outdoor air temperature and Indoor pipe temperature judgment by microcontroller if fulfilled. o When Cooling or Dry mode is operated more than 20 minutes or more. 3 This control stopped if: o Compressor stopped. o Remote control setting changed. (fan speed/temperature) o Outdoor air temperature and indoor intake temperature changed. 13.2.4 Freeze Prevention Control 1 When indoor heat exchanger temperature is lower than 32°F continuously for six minutes, compressor will stop operating. 2 Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 41°F. 3 At the same time, indoor fan speed will be higher than during its normal operation. 4 If indoor heat exchanger temperature is higher than 55.4°F, the fan speed will return to its normal operation. 57

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124

57
13.2.2
Cooling Overload Control
i. Pipe temperature limitation/restriction
Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation
frequency)
The compressor stop if outdoor pipe temperature exceeds 145.4°F.
If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95: outdoor high pressure rise protection)
13.2.3
Dew Prevention Control 1
1
To prevent dew formation at indoor unit discharge area.
2
This control activated if:
o
Outdoor air temperature and Indoor pipe temperature judgment by microcontroller if fulfilled.
o
When Cooling or Dry mode is operated more than 20 minutes or more.
3
This control stopped if:
o
Compressor stopped.
o
Remote control setting changed. (fan speed/temperature)
o
Outdoor air temperature and indoor intake temperature changed.
13.2.4
Freeze Prevention Control
1
When indoor heat exchanger temperature is lower than 32°F continuously for six minutes, compressor will
stop operating.
2
Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 41°F.
3
At the same time, indoor fan speed will be higher than during its normal operation.
4
If indoor heat exchanger temperature is higher than 55.4°F, the fan speed will return to its normal operation.