Panasonic CS-E18SD3UAW service manual - Page 74
H14 Indoor Intake Air Temperature Sensor Abnormality
View all Panasonic CS-E18SD3UAW manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 74 highlights
15.5.3 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting When abnormality indication starts again Check the connector connection: ● Turn off the power ● Check the connector connection Is the connector connection normal? YES Check the indoor intake air temperature sensor: ● Plug out connector from the indoor unit PCB ● Measure the resistance of the indoor intake air temperature sensor Is the measured resistance of the indoor intake air temperature sensor matches the value specified in its characteristic chart? YES Sensor (Thermistor) Characteristics 70 1 Pipe temp. Sensor 60 2 Intake Air Temp. Sensor 50 1 40 2 30 20 10 0 14 32 50 68 86 104 122 Temperature (ºF) For safety reason and to prevent component breakdown, always switch off the power Caution before remove and connect the component. NO ● Connector poor contact ● Correct the connection NO ● Defect in indoor intake air tempeature sensor ● Replace the indoor intake air temperature sensor ● Defect in indoor unit PCB ● Replace the indoor unit PCB Resistance (kΩ) 74