Panasonic CS-E18SD3UAW service manual - Page 76

H16 Outdoor Current Transformer

Page 76 highlights

15.5.5 H16 (Outdoor Current Transformer) Malfunction Decision Conditions  An input current, detected by Current Transformer CT, is below threshold value when the compressor is operating at certain frequency value for 3 minutes. Malfunction Caused  Lack of gas  Broken CT (current transformer)  Broken Outdoor PCB Troubleshooting When abnormality indication starts again Refer to Service Manual Technical Graph for Temp vs Current and Pressure For safety reason and to prevent component Caution breakdown, always switch off the power before remove and connect the component. Suction pressure and running current is normal In forced cooling, check suction pressure versus running current Running current is much too low and suction pressure is much too high Check & replace defected CT Running current and suction is very low Compressor Lack Compression Replace Compressor Check for gas leaking source; Repair or replace defected part(s) Capillary tube/expansion valve blockage; Replace defected part(s) 76

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124

76
15.5.5
H16 (Outdoor Current Transformer)
Malfunction Decision Conditions
An input current, detected by Current Transformer CT, is below threshold value when the compressor is
operating at certain frequency value for 3 minutes.
Malfunction Caused
Lack of gas
Broken CT (current transformer)
Broken Outdoor PCB
Troubleshooting
When abnormality indication starts again
Suction pressure and running current is
normal
Refer to Service Manual Technical Graph
for Temp vs Current and Pressure
In forced cooling, check suction pressure
versus running current
Running current is much too low and
suction pressure is much too high
Running current and suction is
very low
For safety reason and to
prevent component
breakdown, always switch off
the power before remove and
connect the component.
Check & replace defected CT
Compressor Lack Compression
Replace Compressor
Check for gas leaking source; Repair
or replace defected part(s)
Capillary tube/expansion valve
blockage; Replace defected part(s)
Caution