F11 4-way Valve Switching Failure

Page 87 highlights

15.5.16 F11 (4-way Valve Switching Failure) Malfunction Decision Conditions  When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during cooling and compressor operating, the 4-way valve is detected as malfunction. Malfunction Caused  Indoor heat exchanger (pipe) thermistor  4-way valve malfunction Troubleshooting When abnormality starts again Check the indoor pipe temperature thermistor: Plug out connector (CN-TH) from the indoor unit PCB Measure the resistance of the indoor heat exchanger temperature thermistor For safety reason and to prevent component breakdown, always switch off the power before Caution remove and connect the component. Is the measured resistance of the indoor NO pipe temperature thermistor matches the value specified in its characteristic chart? YES Problem occurs in heating mode only? Defect in indoor pipe temperature thermistor Replace the indoor pipe temperature thermistor YES NO, it happen in cooling/dry as well Is 4-way solenoid valve being energised? NO YES Outdoor PCB fault Replace Outdoor PCB The 4-way valve may have been damaged or wrongly connected between discharge and suction tube Check connecting tubes to 4-way valve 4-way valve not working (not energize) Check CN-HOT connection (4-way valve connector) 4 WAYS VALVE YELLOW YELLOW COIL COMPLETE 1 CN-HOT (WHT) 2 No Good Reconnect CN-HOT (4-way valve connector) OK No Check V-coil attach to solenoid valve Good Attach and screw the V-coil to solenoid valve OK No continuity Check valve v-coil continuity (open) V-coil fault Replace Remove CN-HOT. V-coil only CN-HOT (VH9-2) 123 Measure continuity OK of the coil 4 WAYS VALVE Measure voltage supplied to CH-HOT at the start of heating OK (Depending on 4-way valve model) Reverse solenoid valve faulty Replace the 4-way valve No supply Outdoor PCB fault Replace Outdoor PCB * Check gas side pipe - for hot gas flow in cooling mode 87

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124

87
15.5.16 F11 (4-way Valve Switching Failure)
Malfunction Decision Conditions
When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during
cooling and compressor operating, the 4-way valve is detected as malfunction.
Malfunction Caused
Indoor heat exchanger (pipe) thermistor
4-way valve malfunction
Troubleshooting
When abnormality starts again
For safety reason and to prevent component
breakdown, always switch off the power before
remove and connect the component.
Check the indoor pipe temperature
thermistor:
Plug out connector (CN-TH) from the
indoor unit PCB
Measure the resistance of the indoor
heat exchanger temperature thermistor
Is the measured resistance of the indoor
pipe temperature thermistor matches the
value specified in its characteristic chart?
Problem occurs in heating mode only?
Is 4-way solenoid valve being energised?
The 4-way valve may have been damaged
or wrongly connected between discharge
and suction tube
NO, it happen in cooling/dry as well
Check connecting tubes to 4-way valve
4-way valve not working
(not energize)
Check CN-HOT
connection
(4-way valve connector)
Check V-coil attach to
solenoid valve
No
Good
No
Good
No
continuity
(open)
Remove CN-HOT.
Measure continuity
of the coil
Check valve v-coil
continuity
Measure voltage
supplied to CH-HOT at
the start of heating
Outdoor PCB fault
Replace Outdoor PCB
No supply
OK (Depending on 4-way valve model)
Reverse solenoid valve faulty
Replace the 4-way valve
Reconnect CN-HOT
(4-way valve connector)
Attach and screw the V-coil
to solenoid valve
V-coil fault
Replace
V-coil only
YES
YES
YES
NO
NO
OK
OK
OK
Outdoor PCB fault
Replace
Outdoor PCB
4 WAYS VALVE
YELLOW
1
2
CN-HOT
(WHT)
YELLOW
COIL COMPLETE
Defect in indoor pipe temperature
thermistor
Replace the indoor pipe temperature
thermistor
CN-HOT
(VH9-2)
4 WAYS
VALVE
1
2
3
Caution
* Check gas side pipe – for hot gas flow in cooling mode