Panasonic CS-E18SD3UAW service manual - Page 94
F98 Input Over Current Detection
![]() |
View all Panasonic CS-E18SD3UAW manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 94 highlights
15.5.23 F98 (Input Over Current Detection) Malfunction Decision Conditions During operation of cooling and heating, when an input over-current (X value in Total Running Current Control) is detected by checking the input current value being detected by current transformer (CT) with the compressor running. Malfunction Caused Excessive refrigerant. Faulty outdoor unit PCB. Troubleshooting When F98 indication happens Get restarted and measure the input current. Caution For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component. Input current > limit? NO YES Turn off power supply. Check the main circuit electrolytic capacitor. Replace the outdoor unit PCB. Normal? NO Check refrigerant amount. NO Excess refrigerant? NO YES YES Repair the pipe flare or union nuts. Reclaim and recharge refrigerant. Reclaim and recharge with correct amount of refrigerant. Replace outdoor unit PCB Replace outdoor unit compressor 94