Error Codes Table

Page 70 highlights

15.4 Error Codes Table Diagnosis display Abnormality / Protection control H00 No abnormality detected H11 Indoor/outdoor abnormal communication H12 Connection capability rank abnormal H14 Indoor intake air temperature sensor abnormality H15 Outdoor compressor temperature sensor abnormality H16 Outdoor Current Transformer open circuit Abnormality Judgment ─ > 1 min. after starting operation ─ Continue for 5 sec. Continue for 5 sec. ─ H19 Indoor fan motor mechanism lock ─ H21 Indoor float switch operation abnormal H23 Indoor heat exchanger temperature sensor 1 abnormality H24 Indoor heat exchanger temperature sensor 2 abnormality H27 Outdoor air temperature sensor abnormality ─ Continue for 5 sec. Continue for 5 sec. Continue for 5 sec. H28 Outdoor heat exchanger temperature sensor abnormality Continue for 5 sec. H30 Discharge temperature sensor abnormality H32 Outdoor heat exchanger temperature sensor 2 abnormality H34 Outdoor heat sink temperature sensor abnormality H35 Indoor drain water adverse current abnormal Continue for 5 sec. Continue for 5 sec. Continue for 2 sec. ─ H36 Gas pipe temperature sensor abnormality Continue for 5 sec. H37 Outdoor liquid pipe temperature sensor abnormality Continue for 2 sec. H39 Abnormal indoor operating unit or standby units ─ H41 Wiring or piping connection abnormality 3 minutes after compressor start up H97 Outdoor Fan Motor lock abnormality 2 times occurrence within 30 minutes H98 Indoor high pressure protection ─ H99 Indoor heat exchanger anti-freezeing protection F11 Cooling / Heating cycle changeover abnormality ─ 4 times occurrence within 30 minutes F17 Indoor unit freezing error 3 times occurrence within 30 minutes F90 PFC control 4 times occurrence within 10 minutes F91 Refrigeration cycle abnormality 2 times occurrence within 20 minutes F93 Outdoor compressor abnormal revolution 4 times occurrence within 20 minutes F95 Cool high pressure protection 4 times occurrence within 20 minutes F96 IPM (power transistor) overheating protection ─ F97 Outdoor compressor overheating protection 4 times occurrence within 20 minutes Emergency Operation Normal operation Indoor fan operation only ─ ─ ─ ─ ─ ─ O (Cooling only) ─ O Primary location to verify ─  Internal/external cable connections  Indoor/Outdoor PCB ─  Intake air temperature sensor (defective or disconnected)  Compressor temperature sensor (defective or disconnected)  Outdoor PCB  IPM (Power transistor) module  Indoor PCB  Fan motor ─  Heat exchanger temperature sensor 1 (defective or disconnected)  Heat exchanger temperature sensor 2 (defective or disconnected)  Outdoor temperature sensor (defective or disconnected) O  Outdoor heat exchanger temperature sensor (defective or disconnected) ─  Discharge temperature sensor ─  Discharge pipe temperature sensor (defective or disconnected). ─  Outdoor heat sink temperature sensor (defective or disconnected). ─ ─ ─  Gas pipe temperature sensor (defective or disconnected). ─  Outdoor liquid pipe temperature sensor (defective or disconnected). ─ ─ ─ ─ ─  Outdoor PCB  Outdoor Fan Motor ─  Air filter dirty  Air circulation short circuit ─  Insufficient refrigerant  Air filter dirty ─  4-way valve  V-coil  Expansion valve leakage ─  Indoor unit pipe temperature sensor (check for changes in characteristics and check its resistance) ─  Voltage at PFC ─  No refrigerant (3-way valve is closed) ─  Outdoor compressor ─  Outdoor refrigerant circuit  Excess refrigerant ─  Improper heat radiation  IPM (Power transistor) ─  Insufficient refrigerant  Compressor 70

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124

70
15.4 Error Codes Table
Diagnosis
display
Abnormality / Protection control
Abnormality
Judgment
Emergency
Operation
Primary location to verify
H00
No abnormality detected
Normal operation
H11
Indoor/outdoor abnormal communication
> 1 min. after
starting operation
Indoor fan
operation only
Internal/external cable connections
Indoor/Outdoor PCB
H12
Connection capability rank abnormal
H14
Indoor intake air temperature sensor
abnormality
Continue for 5 sec.
Intake air temperature sensor
(defective or disconnected)
H15
Outdoor compressor temperature sensor
abnormality
Continue for 5 sec.
Compressor temperature sensor
(defective or disconnected)
H16
Outdoor Current Transformer open circuit
Outdoor PCB
IPM (Power transistor) module
H19
Indoor fan motor mechanism lock
Indoor PCB
Fan motor
H21
Indoor float switch operation abnormal
H23
Indoor heat exchanger temperature
sensor 1 abnormality
Continue for 5 sec.
O
(Cooling only)
Heat exchanger temperature sensor 1
(defective or disconnected)
H24
Indoor heat exchanger temperature
sensor 2 abnormality
Continue for 5 sec.
Heat exchanger temperature sensor 2
(defective or disconnected)
H27
Outdoor air temperature sensor
abnormality
Continue for 5 sec.
O
Outdoor temperature sensor
(defective or disconnected)
H28
Outdoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
O
Outdoor heat exchanger temperature
sensor (defective or disconnected)
H30
Discharge temperature sensor
abnormality
Continue for 5 sec.
Discharge temperature sensor
H32
Outdoor heat exchanger temperature
sensor 2 abnormality
Continue for 5 sec.
Discharge pipe temperature sensor
(defective or disconnected).
H34
Outdoor heat sink temperature sensor
abnormality
Continue for 2 sec.
Outdoor heat sink temperature sensor
(defective or disconnected).
H35
Indoor drain water adverse current
abnormal
H36
Gas pipe temperature sensor abnormality
Continue for 5 sec.
Gas pipe temperature sensor
(defective or disconnected).
H37
Outdoor liquid pipe temperature sensor
abnormality
Continue for 2 sec.
Outdoor liquid pipe temperature
sensor (defective or disconnected).
H39
Abnormal indoor operating unit or standby
units
H41
Wiring or piping connection abnormality
3 minutes after
compressor start up
H97
Outdoor Fan Motor lock abnormality
2 times occurrence
within 30 minutes
Outdoor PCB
Outdoor Fan Motor
H98
Indoor high pressure protection
Air filter dirty
Air circulation short circuit
H99
Indoor heat exchanger anti-freezeing
protection
Insufficient refrigerant
Air filter dirty
F11
Cooling / Heating cycle changeover
abnormality
4 times occurrence
within 30 minutes
4-way valve
V-coil
F17
Indoor unit freezing error
3 times occurrence
within 30 minutes
Expansion valve leakage
Indoor unit pipe temperature sensor
(check for changes in characteristics
and check its resistance)
F90
PFC control
4 times occurrence
within 10 minutes
Voltage at PFC
F91
Refrigeration cycle abnormality
2 times occurrence
within 20 minutes
No refrigerant
(3-way valve is closed)
F93
Outdoor compressor abnormal revolution
4 times occurrence
within 20 minutes
Outdoor compressor
F95
Cool high pressure protection
4 times occurrence
within 20 minutes
Outdoor refrigerant circuit
F96
IPM (power transistor) overheating
protection
Excess refrigerant
Improper heat radiation
IPM (Power transistor)
F97
Outdoor compressor overheating
protection
4 times occurrence
within 20 minutes
Insufficient refrigerant
Compressor