Panasonic CS-E18SD3UAW service manual - Page 75
H15 Compressor Temperature Sensor Abnormality
View all Panasonic CS-E18SD3UAW manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 75 highlights
15.5.4 H15 (Compressor Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting When abnormality indication starts again Check the connector connection: ● Turn off the power ● Check the connector connection Is the connector connection normal? YES Check the outdoor compressor temperature sensor: ● Plug out connector from the outdoor unit PCB ● Measure the resistance of the outdoor compressor temperature sensor For safety reason and to prevent component breakdown, always switch off the power Caution before remove and connect the component. NO ● Connector poor contact ● Correct the connection Is the measured resistance of the outdoor compressor temperature sensor matches the value specified in its characteristic chart? YES Compressor Temp. Sensor (Thermistor) Characteristics 70 60 50 40 30 20 10 0 68 104 140 176 212 248 284 Temperature (oF) NO ● Defect in outdoor compressor temperature sensor ● Replace the outdoor compressor temperature sensor ● Defect in outdoor unit PCB ● Replace the outdoor unit PCB Resistance (kΩ) 75