Table 4-7, Option 6 and 7 Specifics, Part Number, Attached Power Cord, Attached Plug, Receptacle
View all HP Integrity Superdome SX1000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 132 highlights
System Specifications Electrical Specifications a. A dedicated branch circuit is required for each PDCA installed. Table 4-7 Option 6 and 7 Specifics PDCA Part Number Attached Power Cord Attached Plug Receptacle Required A5201-69023 (Option 6) OLFLEX 190 (PN 600804) is a 2.5 meter multi conductor, 600 volt, 90 degree C, UL and CSA approved, oil resistant flexible cable. (8 AWG 60 A capacity) Mennekes ME 460P9 (60 A capacity) Mennekes ME 460R9 (60 A capacity) A5201-69024 (Option 7) H07RN-F (OLFLEX PN 1600130) is a 2.5 meter heavy duty neoprene jacketed harmonized European flexible cable. (4 mm2 32A capacity) Mennekes ME 532P6-14 (32A capacity) Mennekes ME 532R6-1500 (32 A capacity) NOTE A qualified electrician must wire the PDCA receptacle to site power using copper wire and in compliance with all local codes. Each branch circuit used within a complex must be connected together to form a common ground. When only one PDCA is to be installed in a system cabinet, it must be installed as PDCA0. Refer to Figure 4-1 for PDCA0 location. NOTE When wiring a PDCA, phase rotation is unimportant. When using two PDCAs, however, the rotation must be consistent for both. 120 Chapter 4