HP Integrity Superdome SX1000 User Guide, Sixth Edition - HP Integrity Superdo - Page 145

Power Quality, Sources of Electrical Disturbances, Power System Protection, Distribution Hardware

Page 145 highlights

Site Preparation Electrical and Environmental Guidelines The minimum recommended illumination level is 70 foot-candles (756 lumens per square meter) when the light level is measured at 30 inches (76.2 cm) above the floor. Power Quality This equipment is designed to operate over a wide range of voltages and frequencies. It has been tested and shown to comply with EMC Specification EN50082. However, damage can occur if these ranges are exceeded. Severe electrical disturbances can exceed the design specifications of the equipment. Sources of Electrical Disturbances Electrical disturbances, glitches, affect the quality of electrical power. Common sources of these disturbances are: • Fluctuations occurring within the facility's distribution system • Utility service low-voltage conditions (such as sags or brownouts) • Wide and rapid variations in input voltage levels • Wide and rapid variations in input power frequency • Electrical storms • Large inductive sources (such as motors and welders) • Faults in the distribution system wiring (such as loose connections) • Microwave, radar, radio, or cell phone transmissions Power System Protection Computer systems can be protected from the sources of many of these electrical disturbances by using: • A Protective Earth (PE) connection with a wire diameter of at least equal to the current carrying conductors. The neutral conductor must not be used for the PE connection. (The PE wire is GREEN with a YELLOW stripe.) • A dedicated power distribution system • Power conditioning equipment • Over- and under-voltage detection and protection circuits • Screening to cancel out the effects of undesirable transmissions • Lightning arresters on power cables to protect equipment against electrical storms Every precaution has been taken during power distribution system design to provide immunity to power outages of less than one cycle. However, testing cannot conclusively rule out loss of service. Therefore, adherence to the following guidelines provides the best possible performance of power distribution systems for server equipment: • Dedicated power source-Isolates server power distribution system from other circuits in the facility. • Missing-phase and low-voltage detectors-Shuts equipment down automatically when a severe power disruption occurs. For peripheral equipment, these devices are recommended but optional. • Online uninterruptable power supply (UPS)-Keeps input voltage to devices constant and should be considered if outages of one-half cycle or more are common. Refer to qualified contractors or consultants for each situation. Distribution Hardware This section describes wire selection and the types of raceways (electrical conduits) used in the distribution system. Wire size is dictated by circuit breaker sizing and local safety codes. Chapter 5 133

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150
  • 151
  • 152
  • 153
  • 154
  • 155
  • 156
  • 157
  • 158
  • 159
  • 160
  • 161
  • 162
  • 163
  • 164
  • 165
  • 166
  • 167
  • 168
  • 169
  • 170
  • 171
  • 172
  • 173
  • 174
  • 175
  • 176
  • 177
  • 178
  • 179
  • 180
  • 181
  • 182
  • 183
  • 184
  • 185
  • 186
  • 187
  • 188
  • 189
  • 190
  • 191
  • 192
  • 193
  • 194
  • 195
  • 196
  • 197
  • 198
  • 199
  • 200
  • 201
  • 202
  • 203
  • 204
  • 205
  • 206
  • 207
  • 208
  • 209
  • 210
  • 211
  • 212
  • 213
  • 214
  • 215
  • 216
  • 217
  • 218
  • 219
  • 220
  • 221
  • 222
  • 223
  • 224
  • 225
  • 226
  • 227
  • 228
  • 229
  • 230
  • 231
  • 232
  • 233
  • 234
  • 235
  • 236
  • 237
  • 238
  • 239
  • 240
  • 241
  • 242
  • 243
  • 244
  • 245
  • 246
  • 247
  • 248
  • 249
  • 250
  • 251
  • 252
  • 253
  • 254
  • 255
  • 256
  • 257
  • 258
  • 259
  • 260
  • 261
  • 262
  • 263
  • 264
  • 265
  • 266
  • 267
  • 268
  • 269
  • 270
  • 271
  • 272
  • 273
  • 274
  • 275
  • 276
  • 277
  • 278
  • 279
  • 280
  • 281
  • 282
  • 283
  • 284
  • 285
  • 286
  • 287
  • 288
  • 289
  • 290
  • 291
  • 292
  • 293
  • 294
  • 295
  • 296
  • 297
  • 298
  • 299
  • 300
  • 301
  • 302
  • 303
  • 304
  • 305
  • 306
  • 307
  • 308
  • 309
  • 310
  • 311
  • 312
  • 313
  • 314
  • 315
  • 316
  • 317
  • 318
  • 319
  • 320
  • 321
  • 322
  • 323
  • 324
  • 325
  • 326
  • 327
  • 328
  • 329
  • 330
  • 331
  • 332

Chapter 5
Site Preparation
Electrical and Environmental Guidelines
133
The minimum recommended illumination level is 70 foot-candles (756 lumens per square meter) when the
light level is measured at 30 inches (76.2 cm) above the floor.
Power Quality
This equipment is designed to operate over a wide range of voltages and frequencies. It has been tested and
shown to comply with EMC Specification EN50082. However, damage can occur if these ranges are exceeded.
Severe electrical disturbances can exceed the design specifications of the equipment.
Sources of Electrical Disturbances
Electrical disturbances, glitches, affect the quality of electrical power.
Common sources of these disturbances are:
Fluctuations occurring within the facility’s distribution system
Utility service low-voltage conditions (such as sags or brownouts)
Wide and rapid variations in input voltage levels
Wide and rapid variations in input power frequency
Electrical storms
Large inductive sources (such as motors and welders)
Faults in the distribution system wiring (such as loose connections)
Microwave, radar, radio, or cell phone transmissions
Power System Protection
Computer systems can be protected from the sources of many of these electrical
disturbances by using:
A Protective Earth (PE) connection with a wire diameter of at least equal to the current carrying
conductors. The neutral conductor must not be used for the PE connection. (The PE wire is GREEN with
a YELLOW stripe.)
A dedicated power distribution system
Power conditioning equipment
Over- and under-voltage detection and protection circuits
Screening to cancel out the effects of undesirable transmissions
Lightning arresters on power cables to protect equipment against electrical storms
Every precaution has been taken during power distribution system design to provide immunity to power
outages of less than one cycle. However, testing cannot conclusively rule out loss of service. Therefore,
adherence to the following guidelines provides the best possible performance of power distribution systems
for server equipment:
Dedicated power source—Isolates server power distribution system from other circuits in the facility.
Missing-phase and low-voltage detectors—Shuts equipment down automatically when a severe power
disruption occurs. For peripheral equipment, these devices are recommended but optional.
Online uninterruptable power supply (UPS)—Keeps input voltage to devices constant and should be
considered if outages of one-half cycle or more are common. Refer to qualified contractors or consultants
for each situation.
Distribution Hardware
This section describes wire selection and the types of raceways (electrical conduits) used in the distribution
system. Wire size is dictated by circuit breaker sizing and local safety codes.