HP Integrity Superdome SX1000 User Guide, Sixth Edition - HP Integrity Superdo - Page 135
I/O Expansion Cabinet Power Cords, I/O Expansion Cabinet Power Requirements without Support
View all HP Integrity Superdome SX1000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 135 highlights
System Specifications Electrical Specifications Table 4-10 I/O Expansion Cabinet Power Requirements (without Support Management Station) Requirements Nominal input voltage Input voltage range (minimum-maximum) Frequency range (minimum-maximum) Number of phases Marked Electrical input current Maximum inrush current Power factor correction Value 200/208/220/230/240 (VAC rms) 200-240 (VAC rms) 50/60 (Hz) 1 16A 60 max (A peak) 0.95 minimum Table 4-11 I/O Expansion Cabinet Component Power Requirements Power Required (50 - 60 Hz) VA Fully configured cabinet I/O cardcage ICE 3200 500 600 I/O Expansion Cabinet Power Cords Table 4-12 lists the power cords for the I/O expansion cabinet. Table 4-12 I/O Expansion Cabinet AC Power Cords Part Number A5499AZ -001 -002 Where Used North America International Connector Type L6-20 IEC 309 Chapter 4 123