Installing the System Setting Up the hp Integrity Superdome or hp 9000 Superdome Figure 2-29 Checking PDCA Test Points (5-Wire) See Detail Detail A Detail B Retaining Screw Test Points Table 2-3 4- and 5-Wire Voltage Ranges 4-Wire 5-Wire L2 to L3: 200-240 V L1 to N: 200-240 V L2 to L1: 200-240 V L1 to L3: 200-240 V L2 to N: 200-240 V L3 to N: 200-240 V N to Ground: a a. Neutral to ground voltage can vary from millivolts to several volts depending on the distance to the ground/neutral bond at the transformer. Anything over 3 V should be investigated by a site prep or power specialists. Chapter 2 51