Table 4-15, Typical hp Integrity Superdome Configurations, Memory, Typical, Watts, Cooling, BTU/Hr.
View all HP Integrity Superdome SX1000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 137 highlights
System Specifications Environmental Requirements Table 4-15 Typical hp Integrity Superdome Configurations Cell Memory IO Typical (Watts) Cooling (BTU/Hr.) Breaker Power (Watts)a 3-Pole Breaker Size (Amperes)a,b 4-Pole Breaker Size (Amperes)a,c,d 8 32 4 9790 33406 12335 40 25 8 16 2 8450 28834 10647 40 25 8 8 4 8680 29619 10937 40 25 8 8 2 8170 27878 10294 35 20 8 4 4 8400 28663 10584 35 20 8 4 2 7700 26275 9702 35 20 6 16 4 7370 25149 9286 35 20 6 16 2 6660 22726 8392 30 20 6 8 4 7010 23920 8833 30 20 6 8 2 6300 21497 7938 30 20 6 4 4 6800 23204 8568 30 20 6 4 2 6100 20815 7686 30 20 4 16 4 5880 20064 7409 30 20 4 16 2 5170 17642 6514 30 20 4 8 4 5340 18222 6728 30 20 4 8 2 4630 15799 5834 25 20 4 4 4 5200 17744 6552 25 20 4 4 2 4500 15355 5670 25 20 2 16 2 3800 12967 4788 20 20 2 8 2 3500 11943 4410 20 20 2 4 2 3400 11602 4284 20 20 a. These numbers are valid only for the specific configurations shown. Any upgrades may require a change to the breaker size. A 5-wire source utilizes a 4 pole breaker and a 4-wire source utilizes a 3 pole breaker. The PE (Protective Earth) ground wire is not switched. b. An input power source supplied from a 3-pole plus protective earth (PE), 4-wire system will always be wired as 240 volts phase-to-phase, no neutral or common, plus a PE ground. Three phase input voltage (240VAC) to the equipment is connected phase-to-phase. Examples of 4 wire: 200-volt phase-to-phase, 208-volt phase-to-phase, 220-volt phase-to-phase, 230-volt phase-to-phase, 240-volt phase-to-phase. Chapter 4 125