HP Integrity Superdome SX1000 User Guide, Sixth Edition - HP Integrity Superdo - Page 133
System Power Requirements, PDCA Locations, Table 4-8
View all HP Integrity Superdome SX1000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 133 highlights
Figure 4-1 PDCA Locations System Specifications Electrical Specifications System Power Requirements Table 4-8 and Table 4-9 list the AC power requirements for a hp Integrity Superdome and hp 9000 Superdome systems. These tables provide information to help determine the amount of AC power needed for your computer room. Table 4-8 Power Requirements (without Support Management Station) Requirements Value Comments Nominal input voltage Input voltage range (minimum - maximum) 200/208/220/230/240 (VAC rms) 200 - 240 (VAC rms) Frequency range (minimum - maximum) Number of phases Maximum inrush current Product Label maximum current, three-phase, four-wire 50/60 (Hz) 3 90 (A peak) 44 (A rms) Autoselecting (measured at input terminals) Per phase at 200-240VAC Chapter 4 121