Reference diagram for air-discharge chamber field supply, U-26PES1U6 / U-36PES1U6 / U-42PES1U6
View all Panasonic 26PEK2U6 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 114 highlights
Reference diagram for air-discharge chamber (field supply) 1. Specifications U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6 Required space around outdoor unit If the air discharge chamber is used, the space shown below must be secured around the outdoor unit. If the unit is used without the required space, a protective device may activate, preventing the unit from operating. (1) Single-unit installation Min. 39-3/8 Min. 7-7/8 Unit: inch CAUTION The top and both sides must remain open. If there are obstacles to the front and rear of the outdoor unit, the obstacle at either the front or rear must be no taller than the height of 1 the outdoor unit. (2) Multiple-unit installation Installation in lateral rows More than 15-3/4 More than 11-13/16 More than 7-7/8 More than 11-13/16 Unit: inch CAUTION The front and top must remain open. The obstacles must be no taller than the height of the outdoor unit. Installation in front-rear rows Installation with intakes facing outlets More than 15-3/4 More than 59-1/16 Installation with intakes facing intakes or outlets facing outlets More than 78-3/4 CAUTION The front and both sides must remain open. 1-106 Unit: inch