Alarm P22], In the case of a GND circuit failure inside the motor, the results
View all Panasonic 26PEK2U6 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 255 highlights
(4) [Alarm "P22"] Outdoor unit fan motor drive circuit trouble 4. Service procedures Are connectors CN003 and CN004 connected No correctly to the outdoor unit control PCB? Yes Disconnect connectors CN003 and CN004 No from outdoor unit control PCB, and rotate fan by hand. Does it rotate easily? Yes Correct the connector connections. Outdoor unit fan motor coil resistance is OK if it is as shown below. * Disconnect connector CN004 and No measure on the plug side. (1) Red - white: 30 - 40 Ω (2) White - black: 30 - 40 Ω (3) Black - red: 30 - 40 Ω Yes Motor position detection circuit resistance is OK if it is as shown below. * Disconnect connector CN003 and measure on the plug side. No (1) Grey - yellow: 100 kΩ or more, or ∞ (open) (2) Grey - blue: 100 kΩ or more, or ∞ (open) (3) Grey - orange: 100 kΩ or more, or ∞ (open) 4 Yes Fan motor is OK; outdoor unit control PCB has failed. → Replace. Fan motor trouble → Replace. Note: In the case of a GND circuit failure inside the motor, the results of the above check may be OK. If operation is not OK after the outdoor unit control PCB has been replaced, then replace the outdoor unit fan motor. 4-11