Mounting the Outdoor Unit Alarm History :Display of Outdoor Unit Alarm History
View all Panasonic 26PEK2U6 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 280 highlights
5. Outdoor unit maintenance remote control 5-11. Mounting the Outdoor Unit Alarm History : Display of Outdoor Unit Alarm History • D isplays outdoor unit alarms only. • C heck the indoor unit alarm histories separately using the indoor unit remote controllers or other control device. À Press and hold the (Check) button and button simultaneously for 4 seconds or longer to engage outdoor unit alarm history mode. During temperature monitoring, illuminates.  " Á The display and operations are the same as for the alarm history monitor performed from the indoor unit à remote controller. However the "UNIT No." display shows the outdoor unit address. Á Press the button and select the outdoor unit for which to monitor the alarm history.  Press the temperature setting and buttons and select the item code for the alarm history. ÄÀ The select outdoor unit address, the item code, and the alarm history (alarm data) are displayed. The outdoor unit address is displayed as R.C. XX-YY. System XX = Outdoor unit system address R.C. XX = Outdoor unit system address YY = Outdoor unit sub-bus address Item codes 01-08 are displayed. 01 indicates the most recent alarm. The alarm history displays the alarm code. (If no alarm are present, then -- -- is displayed.) à To clear the alarm history, press the button. (The outdoor unit alarm history will be cleared.) Ä To exit, press the (Check) button. The display returns to the normal display. 5 5-20