Caution, 6-3. Test Run Procedure
View all Panasonic 26PEK2U6 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 287 highlights
Type F2, U2, T2, K2, U1, K1, T1 and F1 6-2. Caution 6. Test run This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit. The indoor and outdoor unit control PCBs utilize a semiconductor memory element (EEPROM). The settings required for operation were made at the time of shipment. Only the correct combination of indoor and outdoor units can be used. This test run manual describes primarily the procedure when using the wired remote controller. 6-3. Test Run Procedure Recheck the items (see 6-4) to check before the test run. Check the combination (wiring) of indoor and outdoor units. (See the section "1-12. ELECTRICAL WIRING".) Turn ON the indoor and outdoor power. Automatic NO address? YES Check the warning code. Set the remote controller to "test run." (See 6-5) Has the test run been NO completed? YES Return the remote controller to normal control. Refer to "Table of Self-Diagnostic Functions and Corrections" to check the system. Note: Check the indoor-side drainage. Fig. 6-3 6 6-3