Panasonic 26PEK2U6 26PEK2U6 Service Manual - Page 247
Service procedures, Possible cause of malfunction
View all Panasonic 26PEK2U6 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 247 highlights
Possible cause of malfunction 4. Service procedures Wired remote control display Wireless remote controller receiver display Operation Timer Standby Ceiling panel connection failure P09 Activation of Indoor protection Fan protective thermostat P01 protective Float switch P10 device Faulty drain pump. Drain pump locked. P11 DC fan error. P12 Outdoor protection Discharge temperature trouble P03 High pressure switch or compressor motor thermal protector is activated. P04 Open phase detected, AC power trouble P05 No gas P15 4-way valve locked P19 High cooling load P20 Outdoor fan trouble P22 Inverter compressor trouble (HIC PCB) P26 Inverter compressor trouble (MDC) P29 Simultaneous-operation multi control trouble P31 Compressor current failure (overload) H01 Thermistor Thermistor open circuit Indoor heat exchanger temperature sensor (E1) F01 fault • Short circuit (indoor) Indoor heat exchanger temperature sensor (E2) F02 Indoor temperature sensor F10 Thermistor open circuit Discharge temperature (TD) F04 • Short circuit (outdoor) Outdoor heat exchanger temperature (C1) F06 Outdoor heat exchanger temperature (C2) F07 Outdoor air temperature (TO) F08 Intake temperature (TS) F12 Indoor EEPROM error F29 Outdoor EEPROM error F31 Alter. Alternately Alter. Alter. Simul. Simul. 4 4-3