Dell PowerConnect Brocade M6505 Brocade 7.1.0 Fabric Watch Administrator's Gui - Page 82

E_Port class default settings, Loss of Synchronization Count

Page 82 highlights

7 portThConfig command procedures • Area: Class 3 (C3) Discards Unlike the other areas, take a conservative approach for the C3 Discards area. Use the default settings and configure the alarms for Above. The goal is to determine the high boundary at which the port would be fenced, so monitor the high boundary and change the settings accordingly. • Area: Trunk Utilization Set the high boundary to 75 percent and the alarms to Above and In-Between conditions. These settings indicate if the 75 percent threshold is exceeded and for how long. • Areas: Primitive Sequence Protocol Error, State Changes, Utilization, Packet Loss Use the default settings. E_Port class default settings Table 17 provides default settings for areas in the E_Port class. Port fencing can be enabled or disabled for the following areas for the E_Port class: • Link Failure Count • Loss of Synchronization Count • Primitive Sequence Protocol Error • Invalid Transmission Word • Invalid CRC Count TABLE 17 E_Port class default settings Area Description Default threshold settings Default alarm settings Threshold state Cyclic redundancy check (CRC) Monitors the number of CRC errors. Invalid transmission Monitors the words (ITW) number of invalid words transmitted. Class 3 discards (C3TX_TO) Link loss Class 3 discards frames due to time out or destination unreachable. Monitors the number of link failures. Unit: Errors Time Base: minute Low: 0 High: 1000 Buffer: 100 Unit: Errors Time Base: minute Low: 0 High: 1000 Buffer: 100 Unit: Errors Time Base: minute Low: 0 High: 5 Buffer: 0 Unit: Errors Time Base: minute Low: 0 High: 500 Buffer: 50 Below: 0 Above: 0 Below: 0 Above: 0 Below: 0 Above: 0 Below: 0 Above: 0 Informative Out_of_range Informative Out_of_range Informative Out_of_range Informative Out_of_range 62 Fabric Watch Administrator's Guide 53-1002752-01

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126

62
Fabric Watch Administrator’s Guide
53-1002752-01
portThConfig command procedures
7
Area: Class 3 (C3) Discards
Unlike the other areas, take a conservative approach for the C3 Discards area. Use the default
settings and configure the alarms for Above. The goal is to determine the high boundary at
which the port would be fenced, so monitor the high boundary and change the settings
accordingly.
Area: Trunk Utilization
Set the high boundary to 75 percent and the alarms to Above and In-Between conditions.
These settings indicate if the 75 percent threshold is exceeded and for how long.
Areas: Primitive Sequence Protocol Error, State Changes, Utilization, Packet Loss
Use the default settings.
E_Port class default settings
Table 17
provides default settings for areas in the E_Port class.
Port fencing can be enabled or disabled for the following areas for the E_Port class:
Link Failure Count
Loss of Synchronization Count
Primitive Sequence Protocol Error
Invalid Transmission Word
Invalid CRC Count
TABLE 17
E_Port class default settings
Area
Description
Default threshold
settings
Default alarm settings
Threshold state
Cyclic redundancy
check (CRC)
Monitors the
number of CRC
errors.
Unit: Errors
Time Base: minute
Low: 0
High: 1000
Buffer: 100
Below: 0
Above: 0
Informative
Out_of_range
Invalid transmission
words (ITW)
Monitors the
number of invalid
words transmitted.
Unit: Errors
Time Base: minute
Low: 0
High: 1000
Buffer: 100
Below: 0
Above: 0
Informative
Out_of_range
Class 3 discards
(C3TX_TO)
Class 3 discards
frames due to time
out or destination
unreachable.
Unit: Errors
Time Base: minute
Low: 0
High: 5
Buffer: 0
Below: 0
Above: 0
Informative
Out_of_range
Link loss
Monitors the
number of link
failures.
Unit: Errors
Time Base: minute
Low: 0
High: 500
Buffer: 50
Below: 0
Above: 0
Informative
Out_of_range