Sanyo 26KHS72R Installation Instructions - Page 13
Tubing Size, Table 1-9, Indoor unit type, 30, 36 types
![]() |
View all Sanyo 26KHS72R manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 13 highlights
H1 07-115 SSHP_II 5/7/07 3:59 PM Page 13 1-5. Tubing Size Single type G Refrigerant tubing between the indoor and outdoor units should be kept as short as possible. G The length of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference between the 2 units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H1) as short as possible. Refer to Table 1-10. Single Main tubing L Table 1-9 Indoor unit type Maximum length Charge-less tubing length (actual length) Additional charge per 1 ft. 26, 30, 36 types 42 type 165 ft. 165 ft. 10 - 100 ft. 15 - 100 ft. 0.43 oz. Maximum indoor-outdoor If outdoor unit is higher H1 height difference If outdoor unit is lower H1 < 100 < 50 13