07-115 SSHP_II 5/7/07 4:00 PM Page 90 8-5. How to Perform Zone Registration To operate the system controller properly, zone registration is required after finishing the test run (and after setting all indoor unit addresses) using one of the following methods. (a) Zone registration using the remote controller (RCS-SH80UG) Refer to page 91. (b) Zone registration using the system controller (SHA-KC64UG) Refer to page 92. (c) Automatic zone registration using the system controller (SHA-KC64UG) Refer to page 93. For methods (a) and (b), you should make a zone registration table manually before performing the registration as shown on the next page. For method (c), zone registration is executed automatically, proceeding from the smallest indoor unit address and smallest central addresses to larger numbers in numerical order. For example: Central address 1 2 3 4 5 6 ZONE-group 1-1 1-2 1-3 1-4 1-5 1-6 Indoor unit address 1-1 1-2 2-1 2-2 2-3 3-1 NOTE 1. An indoor unit address is assigned to each indoor unit during automatic address operation. Each indoor unit address combines an R.C. address and indoor unit number as follows: 1 - 1 : Indoor unit address (UNIT No.) Indoor unit No. Refrigerant circuit No. (R.C. address) 2. This address is displayed on the remote controller for UNIT No. when the UNIT button is pressed. The central address represents the zone and group number. These addresses are assigned in ascending numerical order. SC 90