Sanyo 26KHS72R Installation Instructions - Page 25
Reference diagram for snow-proof vents - 2, Space requirements for setting - 2, CH2672R / 3072R /
![]() |
View all Sanyo 26KHS72R manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 25 highlights
07-115 SSHP_II 5/7/07 3:59 PM Page 25 Reference diagram for snow-proof vents - 2 Space requirements for setting - (2) C(H)2672R / 3072R / 3672R / 4272R with STK-BDRE80A & STK-BDR140U [Obstacles to the front and rear of unit] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit. (1) Single-unit installation Min. P Q Dimension Q If a snow protection duct is attached after the unit is installed, verify that dimension Q is 19-11/16 in. or more. Min. O Outdoor unit C(H)2672R / 3072R / 3672R / 4272R O P 39-3/8 5-29/32 (2) Obstacles on both sides Min. 39-3/8 Min. 7-7/8 Q Min. 11-13/36 Min. 11-13/16 [Installation in front-rear rows] • The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit. Min. 39-3/8 Min. 11-13/16 Min. 59-1/16 Min. 78-3/4 0 Min. 7-7/8 Dimension Q If a snow protection duct is attached after the unit is installed, verify that dimension Q is 19-11/16 in. or more. Unit: inch 25
![](/manual_guide/products/sanyo-26khs72r-installation-instructions-5d29d01/25.png)