07-115 SSHP_II 5/7/07 4:00 PM Page 84 7-23. When Setting Indoor Unit Control PCB Switch for Wall-Mounted Indoor Unit When using either the wired or wireless remote controller, refer to the tables below and accordingly slide the switch on the indoor unit control PCB. G If this setting is not made correctly an alarm will occur. (The operation lamp on the display blinks.) G This setting is not necessary if both the wired remote controller and wireless remote controller are used. However, when you use indoor unit KHS type, set the wired remote controller address connector on the PCB from main to sub position. Wired remote controller G The slide switch setting at the time of factory shipment for model KH type is "A", and for model KHS type is "B." Remote controller address connector Main RCU check Sub RCU. ADR G KH(S)3072 / 3672R, KHH(S)2672R When using wrired A remote controller Nos. 1, 2 OFF, No. 3 ON RC (WL) When using wireless B remote controller Nos. 1, 2, 3 all OFF G KH(S)2672R When using wired A remote controller Nos. 1, 2 OFF, No. 3 ON. When using wireless B remote controller Nos. 1, 2, 3 all OFF 84