Sanyo 26KHS72R Installation Instructions - Page 83
Precautions
View all Sanyo 26KHS72R manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 83 highlights
07-115 SSHP_II 5/7/07 4:00 PM Page 83 7-22. Precautions Request that the customer be present at the time the test run is performed. Explain the Operation Manual to the customer, and then have the customer actually operate the system. Be sure to pass the manual and warranty certificate to the customer. Verify that the AC 208 / 230 V wiring is not connected to the terminal plate which is used to connect the inter-unit control wiring. * If AC 208 / 230 V is accidentally applied to this terminal plate, the fuse (0.5A for both indoor and outdoor units) on the inter-unit control PCB will be tripped in order to protect the PCB. Correct the wiring connections, then disconnect the 2P connectors (indoor unit: blue, OC, CN40; outdoor unit: blue, OC) which are connected to the PCB and connect the other 2P connectors (indoor unit: brown, EMG, CN44; outdoor unit: brown, EMG). (See the figure below.) If operation is still not possible with the brown connectors connected, cut the varistor (black) (for both the indoor and outdoor units). (Be sure to turn OFF the power before performing this work.) Indoor unit control PCB Outdoor unit control PCB VA5 (Varistor, black) 2P connector (brown) EMG, CN44 2P connector (blue) OC, CN40 Fuse 0.5A Fuse 0.5A Varistor (black) Fuse 0.5A 2P connector (blue) 2P connector (brown) SW103 TEST OFF Varistor (black) ON VA002 CHK (2P plug) Serial 1 connector (blue) Serial 2 connector (brown) RC (WL) 83