Sanyo 26KHS72R Installation Instructions - Page 79
Wirin, tem Dia, ram for Grou, Control, Wirin, rocedure, control u, nal receivin
View all Sanyo 26KHS72R manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 79 highlights
07-115 SSHP_II 5/7/07 4:00 PM Page 79 7-17. Wiring System Diagram for Group Control This diagram shows when several units (maximum of 8) are controlled by a signal receiving unit (main unit). In this case, a signal receiving unit can be connected at any indoor unit. Wiring procedure Wire according to the diagram at left: Address setting is executed automatically when the outdoor unit is turned on. Each successive unit will respond at one-second intervals following the order of the group address when the remote controller is operated. Group control using 2 signal receiving units It does not matter which of the 2 signal receiving units you set as the main controller. Remote controller (main) (sub) 12 Connection wiring for group control 12 Wire joint 12 Indoor unit No. 1 U1 U2 12 Indoor unit No. 2 U1 U2 12 Indoor unit No. 3 U1 U2 12 Indoor unit No. 8 U1 U2 When using multiple signal receiving units (up to 2 can be used), one is the main signal receiving unit and the other is the sub-signal receiving unit. To set up a sub-signal receiving unit, change its remote control address connector (RCU. ADR) located on its PCB from main to sub position (main: when shipped from factory). RC (WL) U1 U2 U1 U2 U1 U2 Outdoor unit Outdoor unit Outdoor unit U1 U2 Outdoor unit : Ground (earth) 79