07-115 SSHP_II 5/7/07 4:00 PM Page 87 8-3. Address Switch Setting SW1 Main/sub selection switch OFF: System controller operates as main controller. ON: System controller operates as sub-controller. ALL/ZONE mode selection switch ALL mode: All indoor units can be controlled by system controller ZONE 1, 2, 3, 4 mode: Indoor units in one of zone 1, 2, 3, or 4 can be controlled by system controller. All indoor units cannot be set. 2345 ALL mode OFF OFF OFF ZONE 1 mode OFF OFF ON ZONE 2 mode ON OFF OFF ON ZONE 3 mode OFF ON ON ZONE 4 mode ON ON ON SW1 ON 12345678 OFF Central control/Remote control mode selection switch. OFF: Central control mode. Individual setting by remote controller can be inhibited by system controller. ON: Remote control mode. Setting by system controller is inhibited by other central control equipment. Central control Main/Sub selection switch (OFF: Main, ON: Sub) 1 When AMY adaptor etc. is used with system controller, set the switch to ON position. 2 When only one system controller is used, set the switch to OFF position. 3 Except 1 , when multiple system controllers are used, set only one system controller to OFF position and others to ON position. ALL mode system controller should be in OFF position. (recommended) SC (Central control) button operation switch OFF: (Central control) button operation is permitted. ON : button operation is inhibited. *All switches are in OFF position at shipment. 87