Sanyo 26KHS72R Installation Instructions - Page 63
Wiring System Diagram for Group Control, Wiring procedure, Group control using 2 remote controllers
![]() |
View all Sanyo 26KHS72R manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 63 highlights
07-115 SSHP_II 5/7/07 4:00 PM Page 63 6-4. Wiring System Diagram for Group Control This diagram shows when several units (maximum of 8) are controlled by a remote controller (main unit). In this case, a remote controller can be connected at any indoor unit. I Wiring procedure Wire according to the diagram at right: G Address setting is executed automatically when the outdoor unit is turned on. I Group control using 2 remote controllers It does not matter which of the 2 remote controllers you set as the main controller. When using multiple remote controllers (up to 2 of them can be used), one is the main remote controller and the other is the sub-remote controller. G To set up a sub-remote controller, change its remote control address connector (RCU. ADR) located on its PCB from main to sub position (main: when shipped from factory). Remote controller 12 Wire joint 12 Indoor unit No. 1 U1 U2 Inter-unit control wiring U1 U2 Outdoor unit : Ground (earth) Remote controller (main) (sub) Connection wiring 12 for group control 12 Wire joint 12 Indoor unit No. 1 U1 U2 12 Indoor unit No. 2 U1 U2 12 Indoor unit No. 3 U1 U2 12 Indoor unit No. 8 U1 U2 RC (WD) U1 U2 U1 U2 U1 U2 Outdoor unit Outdoor unit Outdoor unit U1 U2 Outdoor unit : Ground (earth) 63