HP Surestore 64 FW 05.01.00 and SW 07.01.00 Director 2/64 Installation Guide ( - Page 43

Select an Operating Location, Cooling and Power Requirements, Input frequency: 50/60 Hz

Page 43 highlights

Installing and Configuring the Director 2/64 Select an Operating Location Install the director in a secure or limited-access area to ensure that cable connections are not compromised. Also, make sure to install the director in an area with the necessary ventilation and power requirements. Cooling and Power Requirements Two fan modules, each containing three fans (six fans total), provide cooling and redundancy fans for the director. The air intake for the director must satisfy an operating environment temperature requirement of 40°F to 104°F (4°C to 40°C). Director power requirements: ■ Input voltage: 100 to 120 or 200 to 240 VAC ■ Input frequency: 50/60 Hz Caution: Do not block Director 2/64 air vents. The switch uses ambient air for cooling. Director 2/64 Installation Guide 43

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148

Installing and Configuring the Director 2/64
43
Director 2/64 Installation Guide
Select an Operating Location
Install the director in a secure or limited-access area to ensure that cable
connections are not compromised. Also, make sure to install the director in an
area with the necessary ventilation and power requirements.
Cooling and Power Requirements
Two fan modules, each containing three fans (six fans total), provide cooling and
redundancy fans for the director. The air intake for the director must satisfy an
operating environment temperature requirement of 40
°
F to 104°F (4
°
C to 40
°
C).
Director power requirements:
Input voltage: 100 to 120 or 200 to 240 VAC
Input frequency: 50/60 Hz
Caution:
Do not block Director 2/64 air vents. The switch uses ambient air for
cooling.