Fluke 125 Users Manual Performing Harmonics Measurements To perform harmonics measurements do the following: c Connect the inputs as indicated in figure 3-1 Connect input A for VOLT and for WATT, connect input B for AMP and for WATT. 10 mV/A - 1 mV/A BB120 Figure 3-1. Input Connections for Harmonics d Open the application mode menu. e Highlight HARMONICS f Accept your choice. You will see a screen like figure 3-2 If input A was already set to V, and input B was already set to AMP, the actual probe settings will be used. If not, a PROBE menu will be shown to enable you to select the appropriate probe setting. To change the probe settings if the PROBE menu is not automatically opened see Measurement Probes & Settings in chapter 1 . 3-2
Fluke 125
Users Manual
3-2
Performing Harmonics Measurements
To perform harmonics measurements do the following:
Connect the inputs as indicated in figure 3-1
Connect input A for VOLT and for WATT,
connect input B for AMP and for WATT.
BB120
10 mV/A -
1 mV/A
Figure 3-1. Input Connections for Harmonics
Open the application mode menu.
Highlight HARMONICS
Accept your choice. You will see a
screen like figure 3-2
If input A was already set to V, and input B was already set
to AMP, the actual probe settings will be used.
If not, a
PROBE menu will be shown to enable you to select the
appropriate probe setting.
To change the probe settings if the PROBE menu is not
automatically opened see Measurement Probes & Settings
in chapter 1 .