Table 16, Installation, Measurement, Value, Number of, Components, Breaker, Rating, Breaker Type
View all HP Surestore Disk Array FC60 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 149 highlights
Installation Table 16 Disk Enclosure Electrical Requirements Measurement Value Voltage - Range - Frequency 220-240V 100 - 127V 50-60Hz Current - Typical Maximum Operating - 100 - 120 V - 200 - 240 V - Maximum In-rush 2.9 - 3.2A 2.6 - 3.2A 5.3 - 6.7A 20A * In-rush current occurs for 10 to 12 milliseconds HP recommends the use of magnetic-type circuit breakers, which are capable of handling large in-rush currents for short durations (10 to 12 milliseconds) and are rated adequately for the steady state currents. Table 17 Recommended European Circuit Breakers* Number of Breaker Components Rating Breaker Type 1 to 3 16 amps Type C or Type D per IEC 898 or Type K per IEC 947-2 Type D per IEC 898 4 16 amps or Type K per IEC 947-2 * Data assumes no other devices share the circuit breaker. Note Circuit breaker rating must be adequate for the total current drawn by all devices on all electrical paths that share a circuit breaker. Site Requirements 149