Table 32. Particulate contamination specifications (continued) Particulate contamination Specifications NOTE: Air entering the data center must have MERV11 or MERV13 filtration. Conductive dust Air must be free of conductive dust, zinc whiskers, or other conductive particles. NOTE: This condition applies to data center and non-data center environments. Corrosive dust ● Air must be free of corrosive dust. ● Residual dust present in the air must have a deliquescent point less than 60% relative humidity. NOTE: This condition applies to data center and non-data center environments. Table 33. Gaseous contamination specifications Gaseous contamination Specifications Copper coupon corrosion rate
![](/manual_guide/products/dell-poweredge-mx7000-emc-poweredge-mx840c-installation-service-manual-cd200d6/135.png)
Table 32. Particulate contamination specifications (continued)
Particulate contamination
Specifications
NOTE:
Air entering the data center must have MERV11 or MERV13
filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE:
This condition applies to data center and non-data center
environments.
Corrosive dust
●
Air must be free of corrosive dust.
●
Residual dust present in the air must have a deliquescent point less
than 60% relative humidity.
NOTE:
This condition applies to data center and non-data center
environments.
Table 33. Gaseous contamination specifications
Gaseous contamination
Specifications
Copper coupon corrosion rate
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
Silver coupon corrosion rate
<200 Å/month as defined by AHSRAE TC9.9.
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Standard operating temperature
Table 34. Standard operating temperature specifications
Standard operating temperature
Specifications
Continuous operation (for altitude less than 950 m or
3117 ft)
10°C to 35°C (50°F to 95°F) with no direct sunlight on the
equipment.
Humidity percentage range
10% to 80% relative humidity with 29°C (84.2°F) maximum dew
point.
Expanded operating temperature
Table 35. Expanded operating temperature specifications
Expanded operating temperature
Specifications
Continuous operation
5°C to 40°C at 5% to 85% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C to
40°C), the system can operate continuously in temperatures as low
as 5°C and as high as 40°C.
For temperatures between 35°C and 40°C, de-rate maximum
allowable temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
≤ 1% of annual operating hours
–5°C to 45°C at 5% to 90% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C to
40°C), the system can operate down to –5°C or up to 45°C for a
maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C, de-rate maximum
allowable temperature by 1°C per 125 m above 950 m (1°F per 228 ft).