HP StorageWorks MSA2012i HP StorageWorks 2000 Modular Smart Array Reference Gu - Page 302

Power-and-Cooling Module Faults and Recommended Actions, TABLE E-3

Page 302 highlights

Power-and-Cooling Module Faults and Recommended Actions As referred to in TABLE E-1, the following table lists power-and-cooling module faults and recommended actions. TABLE E-3 Power-and-Cooling Module Faults and Recommended Actions Fault Recommended Action Power supply fan warning or failure, or power supply warning or failure. Event code 168 • Check that all of the fans are working using SMU. • Make sure that no slots are left open for more than 2 minutes. If you need to replace a module, leave the old module in place until you have the replacement, or use a blank cover to close the slot. Leaving a slot open negatively affects the airflow and might cause the unit to overhead. • Make sure that the controller modules are properly seated in their slots and that their latches are locked. Power-and-cooling module status is listed as failed or you receive a voltage event notification. Event code 168 • Check that the switch on each power-and-cooling module is turned on. • Check that the power cables are firmly plugged into both power-andcooling modules and into an appropriate electrical outlet. • Replace the power-and-cooling module. AC Power LED is off. Same as above. DC Voltage & Fan Fault/Service LED is on. Replace the power-and-cooling module. 302 HP StorageWorks 2000 Family Modular Smart Array reference guide • August 2008

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150
  • 151
  • 152
  • 153
  • 154
  • 155
  • 156
  • 157
  • 158
  • 159
  • 160
  • 161
  • 162
  • 163
  • 164
  • 165
  • 166
  • 167
  • 168
  • 169
  • 170
  • 171
  • 172
  • 173
  • 174
  • 175
  • 176
  • 177
  • 178
  • 179
  • 180
  • 181
  • 182
  • 183
  • 184
  • 185
  • 186
  • 187
  • 188
  • 189
  • 190
  • 191
  • 192
  • 193
  • 194
  • 195
  • 196
  • 197
  • 198
  • 199
  • 200
  • 201
  • 202
  • 203
  • 204
  • 205
  • 206
  • 207
  • 208
  • 209
  • 210
  • 211
  • 212
  • 213
  • 214
  • 215
  • 216
  • 217
  • 218
  • 219
  • 220
  • 221
  • 222
  • 223
  • 224
  • 225
  • 226
  • 227
  • 228
  • 229
  • 230
  • 231
  • 232
  • 233
  • 234
  • 235
  • 236
  • 237
  • 238
  • 239
  • 240
  • 241
  • 242
  • 243
  • 244
  • 245
  • 246
  • 247
  • 248
  • 249
  • 250
  • 251
  • 252
  • 253
  • 254
  • 255
  • 256
  • 257
  • 258
  • 259
  • 260
  • 261
  • 262
  • 263
  • 264
  • 265
  • 266
  • 267
  • 268
  • 269
  • 270
  • 271
  • 272
  • 273
  • 274
  • 275
  • 276
  • 277
  • 278
  • 279
  • 280
  • 281
  • 282
  • 283
  • 284
  • 285
  • 286
  • 287
  • 288
  • 289
  • 290
  • 291
  • 292
  • 293
  • 294
  • 295
  • 296
  • 297
  • 298
  • 299
  • 300
  • 301
  • 302
  • 303
  • 304
  • 305
  • 306
  • 307
  • 308
  • 309
  • 310
  • 311
  • 312
  • 313
  • 314
  • 315
  • 316
  • 317
  • 318
  • 319
  • 320
  • 321
  • 322
  • 323
  • 324
  • 325
  • 326
  • 327
  • 328
  • 329
  • 330

302
HP StorageWorks 2000 Family Modular Smart Array reference guide
August 2008
Power-and-Cooling Module Faults and
Recommended Actions
As referred to in TABLE E-1, the following table lists power-and-cooling module
faults and recommended actions.
TABLE E-3
Power-and-Cooling Module Faults and Recommended Actions
Fault
Recommended Action
Power supply fan warning
or failure, or
power supply warning or
failure. Event code 168
Check that all of the fans are working using SMU.
Make sure that no slots are left open for more than 2 minutes. If you
need to replace a module, leave the old module in place until you have
the replacement, or use a blank cover to close the slot. Leaving a slot
open negatively affects the airflow and might cause the unit to
overhead.
Make sure that the controller modules are properly seated in their slots
and that their latches are locked.
Power-and-cooling module
status is listed as failed or
you receive a voltage event
notification. Event code
168
Check that the switch on each power-and-cooling module is turned on.
Check that the power cables are firmly plugged into both power-and-
cooling modules and into an appropriate electrical outlet.
Replace the power-and-cooling module.
AC Power LED is off.
Same as above.
DC Voltage & Fan
Fault/Service LED is on.
Replace the power-and-cooling module.