HP Scitex FB10000 Site Preparation Guide Rev. 2 - Page 36
Electrical Requirements
View all HP Scitex FB10000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 36 highlights
Electrical Requirements This section provides the electrical specifications of the HP Scitex FB10000 Industrial Press. Every system may be adapted to the mains power voltage of the country of installation. It is the responsibility of the customer to contact a local, authorized electrician to prepare the site with the proper wiring, circuit breakers, fuses (and power transformer, if necessary), and then connect the HP Scitex FB10000 Industrial Press system to the mains power outlet. The electrician should be available in time for the 2nd day of installation. Electrical Requirements - 50 Hz Table 4-6 shows the electrical requirements of the FB10000 system when using two power inlets, one for the FB10000 itself and one for the UV system. Table 4-6 Electrical Requirements - 50 Hz Unit Phases Connection Type Voltage Input Site Protection Printing unit 3+N+G 5-wire connection 3+N+G 400V between phases 75A (-5% /+10%) 230V between phase & neutral, 50 Hz (-5% /+10%) UV system 3+G 4-wire connection 3 phases + G 400V between phases, 90A 50 Hz (-5% /+10%) Note If the system is powered by a generator, the electrical requirements are the same as for the mains. 28 HP Scitex FB10000 Site Preparation Guide, Rev. 2