HP Scitex FB10000 Site Preparation Guide Rev. 2 - Page 38
Electrical Requirements — 60 Hz, Power Consumption 50 Hz
View all HP Scitex FB10000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 38 highlights
Power Consumption (50 Hz) Table 4-7 shows the estimated power consumption of the FB10000 when operated at full power. Table 4-7 FB10000 Power Consumption (50 Hz) Unit Power Consumption Total Power Consumption Printing unit 58A 40.5 kVA 128A 89.5 kVA UV system 70A 49 kVA Electrical Requirements - 60 Hz Table 4-6 shows the electrical requirements of the FB10000 system when using two power inlets, one for the FB10000 itself and one for the UV system. Table 4-8 Electrical Requirements - 60 Hz Unit Phases Connection Type Voltage Input Site Protection Printing unit 3+N+G UV system 3+G 5-wire connection 3+N+G 4-wire connection 3 phases + G 400V between phases 75A (-5% /+10%) 230V between phase & neutral, 60 Hz (-5% /+10%) 480V between phases, 80A 60 Hz Notes • If the system is powered by a generator, the electrical requirements are the same as for the mains. • The UV system is approved by TUV for 400V and 480V only. In Australia, no transformer is needed if the voltage is a constant 430V. • At 60 Hz sites, make sure to use the correct settings for the UV system and the press, as defined in the FB10000 Installation Guide. 30 HP Scitex FB10000 Site Preparation Guide, Rev. 2