HP Scitex FB10000 Site Preparation Guide Rev. 2 - Page 40

Electrical Diagram - 60 Hz/400V,

Page 40 highlights

Electrical Diagram - 60 Hz/400V Figure 4-7 shows the recommended power connection of the FB10000 system for 60 Hz/400V. Electrical Power network 3 x 400 VAC + N + G, 60Hz Electrical Power network 3 x 400 VAC + N + G, 60Hz L1 L2 L3 N G L1 L2 L3 G Defined by Local Electrician Circuit breaker for printing unit 3 x 75A (75A thermal (In X 7 magnetic) Power Line diameters 4 AWG/75ºC L1 L2 L3 N L1 L2 L3 N Customer site Press Circuit breaker for UV system 3 x 90A (90A thermal (In X 10 magnetic) Power Line diameters 3 AWG/75ºC L1 L2 L3 N L1 L2 L3 N Defined by Local Electrician Customer site Press Press Electrical Cabinet UV Electrical Cabinet Figure 4-7 FB10000 Recommended Power Connections - 60 Hz/400 V) Notes The indicated currents in Figure 4-7 refer to HP-recommended ratings for circuit breakers. For actual power usage values, refer to the power consumption figures in Table 4-7. Use the same type of transformer for the press and the UV system. It is the customer's responsibility to supply the main inlet cable and the inlet cables for the machine and UV system. The length, diameters, and cross section of the power line should be calculated according to the final position of the press to the electrical supply line. Danger The mains power supply to the installation site, all electrical power outlets, and the power line to the machine and UV system must be checked by a qualified licensed electrician for compliance with national and local authority safety requirements. The qualified licensed electrician must also issue and sign a certificate to this effect. 32 HP Scitex FB10000 Site Preparation Guide, Rev. 2

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89

32
HP Scitex FB10000 Site Preparation Guide, Rev. 2
Electrical Diagram — 60 Hz/400V
Figure 4-7
shows the recommended power connection of the FB10000 system for
60 Hz/400V.
Figure 4-7
FB10000 Recommended Power Connections — 60 Hz/400 V)
Notes
The indicated currents in
Figure 4-7
refer to HP-recommended ratings for circuit breakers. For
actual power usage values, refer to the power consumption figures in
Table 4-7
.
Use the same type of transformer for the press and the UV system.
It is the customer’s responsibility to supply the main inlet cable and the inlet cables for the
machine and UV system. The length, diameters, and cross section of the power line should be
calculated according to the final position of the press to the electrical supply line.
Danger
The mains power supply to the installation site, all electrical power outlets, and the power line
to the machine and UV system must be checked by a qualified licensed electrician for
compliance with national and local authority safety requirements. The qualified licensed
electrician must also issue and sign a certificate to this effect.
L1
L2
L3
N
L1
L2
L3
N
L1
L2
L3
N
L1
L2
L3
N
L1
L2
L3
N
G
Press
Electrical Cabinet
UV
Electrical Cabinet
Circuit breaker
for printing unit
3 x 75A
(75A thermal
(In X 7 magnetic)
Circuit breaker
for UV system
3 x 90A
(90A thermal
(In X 10 magnetic)
Electrical Power network
3 x 400 VAC + N + G, 60Hz
Power
Line
diameters
4 AWG/75ºC
Power
Line
diameters
3 AWG/75ºC
Customer site
Press
Defined by Local
Electrician
Defined by Local
Electrician
Customer site
Press
L1
L2
L3
G
Electrical Power network
3 x 400 VAC + N + G, 60Hz