HP Scitex FB10000 Site Preparation Guide Rev. 2 - Page 41

Electrical Diagram - 60 Hz/208V,

Page 41 highlights

Electrical Diagram - 60 Hz/208V Figure 4-8 shows the recommended power connection of the FB10000 system for 60 Hz/208V. Electrical Power network 3 x 208 VAC + G, 60Hz L1 L2 L3 G Electrical Power network 3 x 208 VAC + G, 60Hz L1 L2 L3 G L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 Transformer 55 kVA Primary - 3x208+G 60 Hz Delta Secondary 3x400+N+G Y Transformer 1 Transformer 2 Defined by Local Electrician L1 L2 L3 N Circuit breaker for printing unit 3 x 75A (75A thermal (In X 7 magnetic) L1 L2 L3 N L1 L2 L3 N Circuit breaker for UV system 3 x 80A (80A thermal (In X 10 magnetic) L1 L2 L3 N Transformer 55 kVA Primary - 3x208+G 60hz Delta Secondary 3x480+G Y Defined by Local Electrician Power Line diameters 4 AWG/75ºC Customer site Press Power Line diameters 3 AWG/75ºC Customer site Press Press Electrical Cabinet UV Electrical Cabinet Figure 4-8 FB10000 Recommended Power Connections - 60 Hz/208 V) Notes The indicated currents in Figure 4-8 refer to HP-recommended ratings for circuit breakers. For actual power usage values, refer to the power consumption figures in Table 4-7. Use the same type of transformer for the press and the UV system. It is the customer's responsibility to supply the main inlet cable and the inlet cables for the machine and UV system. The length, diameters, and cross section of the power line should be calculated according to the final position of the press to the electrical supply line. Danger The mains power supply to the installation site, all electrical power outlets, and the power line to the machine and UV system must be checked by a qualified licensed electrician for compliance with national and local authority safety requirements. The qualified licensed electrician must also issue and sign a certificate to this effect. Chapter 4 - Site Planning 33

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89

Chapter 4 - Site Planning
33
Electrical Diagram — 60 Hz/208V
Figure 4-8
shows the recommended power connection of the FB10000 system for
60 Hz/208V.
Figure 4-8
FB10000 Recommended Power Connections — 60 Hz/208 V)
Notes
The indicated currents in
Figure 4-8
refer to HP-recommended ratings for circuit breakers. For
actual power usage values, refer to the power consumption figures in
Table 4-7
.
Use the same type of transformer for the press and the UV system.
It is the customer’s responsibility to supply the main inlet cable and the inlet cables for the
machine and UV system. The length, diameters, and cross section of the power line should be
calculated according to the final position of the press to the electrical supply line.
Danger
The mains power supply to the installation site, all electrical power outlets, and the power line
to the machine and UV system must be checked by a qualified licensed electrician for
compliance with national and local authority safety requirements. The qualified licensed
electrician must also issue and sign a certificate to this effect.
L1
L2
L3
L1
L2
L3
L1
L2
L3
N
L1
L2
L3
N
L1
L2
L3
N
L1
L2
L3
N
Press
Electrical Cabinet
UV
Electrical Cabinet
Circuit breaker
for printing unit
3 x 75A
(75A thermal
(In X 7 magnetic)
Power
Line
diameters
4 AWG/75ºC
Power
Line
diameters
3 AWG/75ºC
Customer site
Press
Transformer 1
L1
L2
L3
L1
L2
L3
Electrical Power network
3 x 208 VAC + G, 60Hz
Transformer 2
L1
L2
L3
G
Transformer 55 kVA
Primary - 3x208+G 60 Hz Delta
Secondary 3x400+N+G Y
Transformer 55 kVA
Primary - 3x208+G 60hz Delta
Secondary 3x480+G Y
Circuit breaker
for UV system
3 x 80A
(80A thermal
(In X 10 magnetic)
Defined by Local
Electrician
Customer site
Press
Defined by Local
Electrician
Electrical Power network
3 x 208 VAC + G, 60Hz
L1
L2
L3
G