2-9 Rack-Mount Bezel The rack-mount bezel (rack model only) must be removed to replace the power switch. To remove the rack-mount bezel: 1. Perform the preparation procedures. See "Preparation Procedures" earlier in this chapter. 2. Remove the seven T-15 screws securing the rack-mount bezel to the chassis. 3. Pull the rack-mount bezel away from the chassis. Figure 2-5. Removing the rack-mount bezel NOTE: Drive cage may not be as illustrated. Reverse steps 1 through 3 to replace the rack-mount bezel. Compaq ProLiant 3000 Servers, for use with Intel 350 MHz or greater processor-based servers only, Maintenance and Service Guide
2-9
Compaq ProLiant 3000 Servers, for use with Intel 350 MHz or greater processor-based servers only, Maintenance and Service Guide
Rack-Mount Bezel
The rack-mount bezel (rack model only) must be removed to replace the power switch.
To remove the rack-mount bezel:
1.
Perform the preparation procedures. See “Preparation Procedures” earlier in this chapter.
2.
Remove the seven T-15 screws securing the rack-mount bezel to the chassis.
3.
Pull the rack-mount bezel away from the chassis.
Figure 2-5. Removing the rack-mount bezel
NOTE
:
Drive cage may not be as illustrated.
Reverse steps 1 through 3 to replace the rack-mount bezel.