HP ProLiant 3000 ProLiant 3000 Servers Maintenance and Service Guide - Page 99

FYI: Drive bay X, Configuration Utility.

Page 99 highlights

3-42 Diagnostic Tools DAAD Diagnostic Messages Continued Message Description Drive (bay) X was inadvertently replaced The physical drive was incorrectly replaced after another drive failed. Recommended Action Replace the drive that was incorrectly replaced and replace the original drive that failed. Do not run the System Configuration Utility and try to reconfigure; data will be lost. Duplicate write memory error Data could not be written to the array accelerator board in duplicate due to the detection of parity errors. This is not a data loss situation. Replace the array accelerator board. Error occurred reading RIS copy from drive (bay) X An error occurred while DAAD was trying to read the RIS from this drive. If there were multiple errors, this drive may need to be replaced. FYI: Drive (bay) X is non-Compaq supplied The installed drive was not supplied by Compaq. If problems exist with this drive, replace it with a Compaq drive. Identify controller data did not match with NVRAM The identify controller data from the array controller did not match the information stored in nonvolatile RAM. This could occur if new, previously configured drives have been placed in a system that has also been previously configured. It could also occur if the firmware on the controller has been upgraded and the System Configuration Utility was not run. Check the identify controller data under the Inspect Utility. If the firmware version field is the only thing different between the controller and nonvolatile RAM data, this is not a problem. Otherwise, run the System Configuration Utility. Identify logical drive data did not match with NVRAM The identify unit data from the array controller did not match with the information stored in nonvolatile RAM. This could occur if new, previously configured drives have been placed in a system that has also been previously configured. Run the System Configuration Utility to configure the controller and nonvolatile RAM. Insufficient adapter resources The adapter does not have sufficient resources to perform operations to the array accelerator board. Drive rebuild may be occurring. Operate the system without the array accelerator board until the drive rebuild completes. Continued

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150
  • 151
  • 152
  • 153
  • 154
  • 155
  • 156
  • 157
  • 158
  • 159
  • 160
  • 161
  • 162

3-42
Diagnostic Tools
DAAD Diagnostic Messages
Continued
Message
Description
Recommended Action
Drive (bay) X was
inadvertently
replaced
The physical drive was incorrectly
replaced after another drive failed.
Replace the drive that was incorrectly replaced and
replace the original drive that failed. Do not run the
System Configuration Utility and try to reconfigure; data
will be lost.
Duplicate write
memory error
Data could not be written to the array
accelerator board in duplicate due to
the detection of parity errors. This is not
a data loss situation.
Replace the array accelerator board.
Error occurred
reading RIS copy
from drive (bay) X
An error occurred while DAAD was
trying to read the RIS from this drive.
If there were multiple errors, this drive may need to be
replaced.
FYI: Drive (bay) X
is non-Compaq
supplied
The installed drive was not supplied by
Compaq.
If problems exist with this drive, replace it with a
Compaq drive.
Identify controller
data did not
match with
NVRAM
The identify controller data from the
array controller did not match the
information stored in nonvolatile RAM.
This could occur if new, previously
configured drives have been placed in a
system that has also been previously
configured. It could also occur if the
firmware on the controller has been
upgraded and the System Configuration
Utility was not run.
Check the identify controller data under the Inspect
Utility. If the firmware version field is the only thing
different between the controller and nonvolatile RAM
data, this is not a problem. Otherwise, run the System
Configuration Utility.
Identify logical
drive data did not
match with
NVRAM
The identify unit data from the array
controller did not match with the
information stored in nonvolatile RAM.
This could occur if new, previously
configured drives have been placed in a
system that has also been previously
configured.
Run the System Configuration Utility to configure the
controller and nonvolatile RAM.
Insufficient
adapter resources
The adapter does not have sufficient
resources to perform operations to the
array accelerator board. Drive rebuild
may be occurring.
Operate the system without the array accelerator board
until the drive rebuild completes.
Continued