HP Surestore Disk Array FC60 HP SureStore E Disk Array FC60 Service Manual (A5 - Page 115
Table 8, Installation, Operating, Current, In-Rush, Power, Cords, Measurement, Value @ 110v
View all HP Surestore Disk Array FC60 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 115 highlights
Installation Table 8 Total Operating and In-Rush Currents Operating Current @ 110v Operating Current @ 220v Controller w/ 6 Disk Enclosures 41.3A Controller w/ 5 Disk Enclosures 34.8A Controller w/ 4 Disk Enclosures 28.3A Controller w/ 3 Disk Enclosures 21.8A Controller w/ 2 Disk Enclosures 15.3A Controller w/ 1 Disk Enclosure 8.8 * In-rush current occurs for 10 to 12 milliseconds 20.4A 17.2A 14.0A 10.8A 7.6 4.4A In-Rush* Power Current Cords 124A 14 104A 12 84A 10 64A 8 44A 6 24A 4 Table 9 Controller Enclosure Electrical Requirements Measurement Value @ 110v Value @ 220v Voltage - Range - Frequency Current - Typical - Maximum Operating - Inrush 100-127V 50 - 60 Hz 1.5A 2.3A 21.4A 220-240V 50 - 60 Hz 0.8A 1.2A 42.9A Site Requirements 115
Site Requirements
115
Installation
*
In-rush current occurs for 10 to 12 milliseconds
Table 8
Total Operating and In-Rush Currents
Operating
Current
@ 110v
Operating
Current
@ 220v
In-Rush
*
Current
Power
Cords
Controller w/ 6 Disk Enclosures
41.3A
20.4A
124A
14
Controller w/ 5 Disk Enclosures
34.8A
17.2A
104A
12
Controller w/ 4 Disk Enclosures
28.3A
14.0A
84A
10
Controller w/ 3 Disk Enclosures
21.8A
10.8A
64A
8
Controller w/ 2 Disk Enclosures
15.3A
7.6
44A
6
Controller w/ 1 Disk Enclosure
8.8
4.4A
24A
4
Table 9
Controller Enclosure Electrical Requirements
Measurement
Value @ 110v
Value @ 220v
Voltage
– Range
– Frequency
100-127V
50 - 60 Hz
220-240V
50 - 60 Hz
Current
– Typical
–
Maximum Operating
– Inrush
1.5A
2.3A
21.4A
0.8A
1.2A
42.9A