Troubleshooting Disk Array Installation/Troubleshooting Checklist The following checklist is intended to help isolate and solve problems that may occur when installing the disk array. • Check for Physical Damage: - Disk array packaging and disk array components undamaged - Cabinet packaging and cabinet undamaged • Check Site Power - Proper use of ground and neutral with correct gauge wire - Neutral to ground voltage less than 3 volts - Ground connected to main service panel with correct gauge wire - Raised floor properly grounded - No single wire daisy chaining of ground between power receptacles - Power source used exclusively by computer room - No power surges or sags - Proper voltage on all phases - Other (RFI/EMI) • Check Site Environment: - Ambient temperature within specifications (20° C to 25.5° C (68° F to 78° F)) - Perforated tiles properly placed to enhance proper airflow - No temperature hot spots within computer room - Humidity within specifications (40% to 60% non-condensing) - Proper clearance between surrounding products Disk Array Installation/Troubleshooting Checklist 211