HP Surestore Disk Array FC60 HP SureStore E Disk Array FC60 Service Manual (A5 - Page 369
AC Power:, Heat Output:, AC Voltage and Frequency, Current, Power Consumption
View all HP Surestore Disk Array FC60 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 369 highlights
Reference / Legal / Regulatory AC Power: AC Voltage and Frequency: • 120 VAC (100 - 127 VAC), 50 to 60 Hz single phase • 230 VAC (220 - 240 VAC), 50 to 60 Hz single phase • Auto-ranging Current: Voltage 100 - 127 VAC 220 - 240 VAC Typical Operating Current 1.5 A 0.8 A Maximum In-Rush Current Operating Current 2.3 A 1.2 A 21.7 A 42.9 A HP recommends the use of magnetic-type circuit breakers, which are capable of handling large in-rush currents for short durations (10 to 12 milliseconds) and are rated adequately for the steady state currents. Power Consumption: Incoming Voltage AC RMS Typical Power Consumption 100- 127 VAC 200 - 240 VAC 180 watts 180 watts Heat Output: • 615 BTU/hr. A5635A Controller Enclosure Specifications 369
A5635A Controller Enclosure Specifications
369
Reference / Legal /
Regulatory
AC Power:
AC Voltage and Frequency:
•
120 VAC (100 - 127 VAC),
50 to 60 Hz single phase
•
230 VAC (220 - 240 VAC),
50 to 60 Hz single phase
•
Auto-ranging
Current:
HP recommends the use of magnetic-type circuit breakers, which are capable of handling
large in-rush currents for short durations (10 to 12 milliseconds) and are rated adequately
for the steady state currents.
Power Consumption:
Heat Output:
•
615 BTU/hr.
Voltage
Typical
Operating
Current
Maximum
Operating Current
In-Rush Current
100 - 127 VAC
1.5 A
2.3 A
21.7 A
220 - 240 VAC
0.8 A
1.2 A
42.9 A
Incoming Voltage
AC RMS
Typical Power Consumption
100- 127 VAC
180 watts
200 - 240 VAC
180 watts