Grounding, Circuit Breaker, Power Options, WARNING, Table 2-6 Available Power Options
View all HP Superdome SX2000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 51 highlights
Grounding The site building must provide a safety ground or protective earth for each ac service entrance to all cabinets. WARNING! This equipment is Class 1 and requires full implementation of the grounding scheme to all equipment connections. Failure to attach to protective earth results in loss of regulatory compliance and creates a possible safety hazard. Circuit Breaker Each cabinet using a 3-phase, 4-wire input requires a dedicated circuit breaker to support the Marked Electrical current of 44 A per phase. The facility electrician and local service codes determine proper circuit breaker selection. Each cabinet using a 3-phase, 5-wire input requires a dedicated circuit breaker to support the Marked Electrical current of 24 A per phase. The facility electrician and local service codes determine proper circuit breaker selection. NOTE: When using the minimum-size breaker, always choose circuit breakers with the maximum allowed trip delay to avoid nuisance tripping. Power Options Table 2-6 describes the available power options. Table 2-7 provides details about the available options. The options listed are consistent with options for earlier Superdome systems. Table 2-6 Available Power Options Option Source Type Source Voltage (Nominal) PDCA Input Current Per Power Receptacle Required Required Phase 200 to 240 V ac 1 6 3-phase Voltage range 200 to 240 4-wire 44 A maximum per Connector and plug provided V ac, phase-to-phase, 50 phase with a 2.5 meter (8.2 feet) power Hz/60 Hz cable. Electrician must hardwire the receptacle to 60 A site power. 7 3-phase Voltage range 200 to 240 5-wire 24 A maximum per Connector and plug provided V ac, phase-to-neutral, phase with a 2.5 meter (8.2 feet) power 50 Hz/60 Hz cable. Electrician must hardwire the receptacle to 32 A site power. 1 A dedicated branch circuit is required for each PDCA installed. Table 2-7 Option 6 and 7 Specifics PDCA Part Number A5201-69023 (Option 6) A5201-69024 (Option 7) Attached Power Cord Attached Plug Receptacle Required OLFLEX 190 (PN 600804) is a 2.5 meter (8.2 feet) multiconductor, 600 V, 90˚ C, UL and CSA approved, oil resistant flexible cable (8 AWG 60 A capacity). Mennekes ME 460P9 (60 A capacity) H07RN-F (OLFLEX PN 1600130) is a 2.5 meter (8.2 feet) Mennekes ME heavy-duty neoprene-jacketed harmonized European 532P6-14 (32 A flexible cable (4 mm2 32 A capacity). capacity) Mennekes ME 460R9 (60 A capacity) Mennekes ME 532R6-1500 (32 A capacity) Electrical Specifications 51